To open the short circuiting device :
1.
Make sure that the current transformer secondary circuits are complete.
Do not open circuit the secondary of an energized breaker.
2.
a)
Single Ratio
-
Remove and store the shorting screw
¬
.
Do not remove the ground screw
-
.
b)
Multi Ratio -
Remove the shorting screw
¬
.
Insert shorting screw
¬
according to connection diagram.
Do not remove the ground screw
-
.
Figure 22. Short Circuiting Device