![ABB Johnson Controls AYK550-UH Скачать руководство пользователя страница 327](http://html.mh-extra.com/html/abb/johnson-controls-ayk550-uh/johnson-controls-ayk550-uh_user-manual_3352327.webp)
A
<.
550-UH User’s Manual
1-327
Technical data
Degrees of protection
Available enclosures:
•
UL type 1 (NEMA 1 / IP 21) enclosure. The site must be free of airborne dust,
corrosive gases or liquids, and conductive contaminants such as condensation,
carbon dust, and metallic particles.
•
UL type 12 (NEMA 12 / IP 54) enclosure. This enclosure provides protection from
airborne dust and light sprays or splashing water from all directions.
Compared to the UL type 1 enclosure, the UL type 12 enclosure has:
•
The same internal plastic shell as the UL type 1 enclosure
•
A different outer plastic cover
•
An additional internal fan to improve cooling
•
Larger dimensions
•
The same rating (does not require a derating).
Plenum Rating: A
<.
550 drives (UL type 1 & 12) have been evaluated in accordance
with the requirements of UL508, meets all of the requirements for plenum rated
drives, and is “Suitable for Installation in a Compartment Handling Conditioned Air”.