![ABB Johnson Controls AYK550-UH Скачать руководство пользователя страница 223](http://html.mh-extra.com/html/abb/johnson-controls-ayk550-uh/johnson-controls-ayk550-uh_user-manual_3352223.webp)
A
<.
550-UH User’s Manual
1-223
Embedded fieldbus
a. Points not listed are not used in this application.
b. A single value in a column means that the value is the same in English units and in SI units.
c. Point numbers that appear in brackets { } may be unbundled at the field panel.
Detailed point descriptions
{91}
LAI
PREV FAULT 1
-
-
1
0
-
-
{92}
LAI
PREV FAULT 2
-
-
1
0
-
-
{93}
LDI
OK.FAULT
OK
-
1
0
FAULT
OK
{94}
LDO
RESET FAULT
NO
-
1
0
RESET
NO
{95}
LAO
MBOX PARAM
-
-
1
0
-
-
{96}
LAO
MBOX DATA
-
-
1
0
-
-
{97}
LDO
MBOX READ
DONE
-
1
0
READ
DONE
{98}
LDO
MBOX WRITE
DONE
-
1
0
WRITE
DONE
{99}
LAO
ERROR STATUS
-
-
1
0
-
-
FLN Detailed Point Descriptions
Point
Description
Drive
Parameter
1
CTRL ADDRESS
The FLN address of the drive. It can be set by FLN and by
the panel.
5302
2
APPLICATION
The Application ID for FLN on the A
YK
550. This ID is
assigned by Siemens for each unique application. It
correlates directly to a particular point list approved at the
time of release. Therefore, this point list shall remain fixed
once approval is granted. Any changes to the point list shall
require a new Application ID and re-approval by Siemens.
The Application ID assigned to A
YK
550 is 2934.
3
FREQ OUTPUT
The output frequency applied to the motor, in Hertz.
0103
4
PCT OUTPUT
The ratio of output frequency or speed to the corresponding
maximum rating, depending on control mode.
• For scalar mode, it is the ratio of Output Frequency
(parameter 0103) to Maximum Frequency (parameter
2008).
• For speed mode, it is the ratio Speed (parameter 0102) to
Maximum Speed (2002).
None. This
ratio is
calculated
by the FLN
application.
5
SPEED
The calculated speed of the motor, in RPM.
0102
6
CURRENT
The measured output current.
0104
7
TORQUE
The calculated output torque of the motor as a percentage of
nominal torque.
0105
8
POWER
The measured output power in KW. The FLN point definition
also supports horsepower by selecting English units.
0106
9
DRIVE TEMP
The measured heatsink temperature, in
°
C. The FLN point
definition also supports
°
F by selecting English units.
0110
FLN Point Database
Point
Subpoint Name
Factory
Default
Engr.
Units
Slope
Intercept
On Text
Off Text
#
Type
(SI Units)
Содержание Johnson Controls AYK550-UH
Страница 2: ......
Страница 8: ...1 8 A 550 UH User s Manual Table of contents ...
Страница 32: ...1 32 A 550 UH User s Manual Installation ...
Страница 66: ...1 66 A 550 UH User s Manual Application macros ...
Страница 186: ...1 186 A 550 UH User s Manual Parameters ...
Страница 190: ...1 190 A 550 UH User s Manual Embedded fieldbus Preferred wiring diagram Alternate wiring diagram ...
Страница 333: ...A 550 UH User s Manual 1 333 Technical data ...