Parameters
Group 98: OPTIONS
This group configures for options, in particular, enabling serial communication with
the drive.
Group 98: Options
Code Description Range
Resolution
Default
S
9802
COMM PROT SEL
0…5
1
0 (
NOT
SEL
)
Selects the communication protocol.
0 =
NOT
SEL
– No communication protocol selected.
1 =
STD
MODBUS
– The drive communicates with Modbus via the RS485 channel (X1-communications, terminal).
• See also
2 =
N
2 – Enables fieldbus communication with the drive using Metasys N2 protocol via the RS485 serial link (X1-
communications terminal).
3 =
FLN
– Enables fieldbus communication with the drive using FLN protocol via the RS485 serial link (X1-
communications terminal).
4 =
EXT
FBA
– The drive communicates via a fieldbus adapter module in option slot 2 of the drive.
• See also
.
5 =
BACNET
– Enables fieldbus communication with the drive using BACnet protocol via the RS485 serial link (X1-
communications terminal).
Содержание Johnson Controls AYK550-UH
Страница 2: ......
Страница 8: ...1 8 A 550 UH User s Manual Table of contents ...
Страница 32: ...1 32 A 550 UH User s Manual Installation ...
Страница 66: ...1 66 A 550 UH User s Manual Application macros ...
Страница 186: ...1 186 A 550 UH User s Manual Parameters ...
Страница 190: ...1 190 A 550 UH User s Manual Embedded fieldbus Preferred wiring diagram Alternate wiring diagram ...
Страница 333: ...A 550 UH User s Manual 1 333 Technical data ...