A
<.
550-UH User’s Manual
1-183
Parameters
8123
PFA ENABLE
0, 1
1
0 (
NOT
SEL
)
Selects PFA control. When enabled, PFA control:
• Switches in, or out, auxiliary constant speed motors as output demand increases or decreases. Parameters 8109
START
FREQ
1 to 8114
LOW
FREQ
3 define the switch points in terms of the drive output frequency.
• Adjusts the speed regulated motor output down, as auxiliary motors are added, and adjusts the speed regulated
motor output up, as auxiliary motors are taken off line.
• Provides Interlock functions, if enabled.
• Requires 9904
MOTOR
CTRL
MODE
= 3 (
SCALAR
:
FREQ
).
0 =
NOT
SEL
– Disables PFA control.
1 =
ACTIVE
– Enables PFA control.
8124
ACC IN AUX STOP
0.0…1800.0 s
0.1 s
0.0 s (
NOT
SEL
)
Sets the PFA acceleration time for a zero-to-maximum
frequency ramp. This PFA acceleration ramp:
• Applies to the speed regulated motor, when an auxiliary
motor is switched off.
• Replaces the acceleration ramp defined in
.
• Applies only until the output of the regulated motor
increases by an amount equal to the output of the
switched off auxiliary motor. Then the acceleration ramp
defined in
applies.
0 =
NOT
SEL
.
0.1…1800 – Activates this function using the value
entered as the acceleration time.
• A = speed regulated motor accelerating using
parameters (2202 or 2205).
• B = speed regulated motor decelerating using
parameters (2203 or 2206).
• At aux. motor start, speed regulated motor decelerates using 8125
DEC
IN
AUX
START
.
• At aux. motor stop, speed regulated motor accelerates using 8124
ACC
IN
AUX
STOP
.
8125
DEC IN AUX START
0.0…1800.0 s
0.1 s
0.0 s (
NOT
SEL
)
Sets the PFA deceleration time for a maximum-to-zero frequency ramp. This PFA deceleration ramp:
• Applies to the speed regulated motor, when an auxiliary motor is switched on.
• Replaces the deceleration ramp defined in
.
• Applies only until the output of the regulated motor decreases by an amount equal to the output of the auxiliary
motor. Then the deceleration ramp defined in
applies.
0 =
NOT
SEL
.
0.1…1800 – Activates this function using the value entered as the deceleration time.
• See parameter 8124.
8126
TIMED AUTOCHNG
0…4
1
0 (
NOT
SEL
)
Sets the autochange using a Timed function. See parameter 8119
AUTOCHNG
LEVEL
.
0 =
NOT
SEL
.
1 =
TIMED
FUNC
1 – Enables autochange when Timed function 1 is active.
2…4 =
TIMED
FUNC
2…4 – Enables autochange when Timed function 2…4 is active.
8127
MOTORS
1…7
1
2
Sets the actual number of PFA controlled motors (maximum 7 motors, 1 speed regulated, 3 connected direct-on-line
and 3 spare motors).
• This value includes also the speed regulated motor.
• This value must be compatible with the number of relays allocated to PFA if the Autochange function is used.
• If Autochange function is not used, the speed regulated motor does not need to have a relay output allocated to
PFA but it needs to be included in this value.
Group 81: PFA Control
Code Description Range
Resolution
Default
S
P 8125
P 8124
A
B
1
0
Aux.
motor
f
OUT
t
t
Содержание Johnson Controls AYK550-UH
Страница 2: ......
Страница 8: ...1 8 A 550 UH User s Manual Table of contents ...
Страница 32: ...1 32 A 550 UH User s Manual Installation ...
Страница 66: ...1 66 A 550 UH User s Manual Application macros ...
Страница 186: ...1 186 A 550 UH User s Manual Parameters ...
Страница 190: ...1 190 A 550 UH User s Manual Embedded fieldbus Preferred wiring diagram Alternate wiring diagram ...
Страница 333: ...A 550 UH User s Manual 1 333 Technical data ...