102
24V DC
Fuse,
3A, Type T
Terminal Block E
1
2
3
4
5
6
7
8
+
-
Terminal Block E
L
N
85 min. to 265V max.
50/60Hz
1
2
3
4
5
6
7
8
Line
Neutral
Fuse,
315mA, Type T
17
18
19
14
15
16
11
12
13
7
8
9
4
5
6
1
2
3
Terminal Block C or D
NC
NO
C
Digital Output
Common
Load
9
10
11
12
13
14
15
16
do1
do2
do3
do4
do5
do6
COM
COM
di1
di2
di3
di4
di5
di6
COM
COM
Terminal Blocks C or D
Input State
Dxx active
Switch Input
(volt-free)
or
or
5V
0V
Logic Input
(TTL)
Logic State
Dxx inactive
1
2
3
4
5
6
7
8
5V
or
0V
a01
a02
17
18
19
20
+
–
+
–
…5
INSTALLATION
Warning.
Use fuse rating – 315mA (max.) type T.
A - A.C. Supply
Note.
Relay contacts are fitted with arc suppression
components as standard.
Fig. 5.10 Relay Connections
Note.
Voltage level:
5V.
Load:
450
min.
15k
max.
Fig. 5.11 Digital Output Connections
Fig. 5.12 Digital Input Connections
Fig. 5.13 Analog Output Connections
5.6
Mains Power Connections – Fig. 5.9
5.7
Relay Output Board Connections – Fig. 5.10
Notes.
• The maximum total combined current flowing
through the relays is 36A. The maximum individual
relay current is 5A.
• The polarity is set up during I/O module
configuration – see Section 4.7.2.
5.8
Hybrid I/O Module Connections
5.8.1
Digital Output Connections – Fig. 5.11
Six digital outputs are provided on the Hybrid option board.
5.8.2
Digital Input Connections – Fig. 5.12
Six digital inputs are provided on Hybrid option boards.
5.8.3
Analog Output Connections – Fig. 5.13
Two analog outputs are provided on the Hybrid option board.
Warning.
Use fuse rating – 3A (max.) type T.
B - D.C. Supply
Fig. 5.9 Mains Power Supply