4.2.2
IED commands for IEC 60870-5-103 I103IEDCMD
4.2.2.1
Functionality
GUID-19AD44B2-21D6-4DB0-AD74-1578DA30C100 v5
I103IEDCMD is a command block in control direction with defined IED functions.
All outputs are pulsed and they are NOT stored. Pulse length is fixed to 400ms.
4.2.2.2
Function block
GUID-52D27CDA-8805-48FA-99BE-2E05A438B0C7 v1
IEC10000283-1-en.vsd
I103IEDCMD
BLOCK
19-LEDRS
23-GRP1
24-GRP2
25-GRP3
26-GRP4
IEC10000283 V1 EN-US
Figure 14:
I103IEDCMD function block
4.2.2.3
Signals
PID-3788-INPUTSIGNALS v5
Table 32:
I103IEDCMD Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of commands
PID-3788-OUTPUTSIGNALS v5
Table 33:
I103IEDCMD Output signals
Name
Type
Description
19-LEDRS
BOOLEAN
Information number 19, reset LEDs
23-GRP1
BOOLEAN
Information number 23, activate setting group 1
24-GRP2
BOOLEAN
Information number 24, activate setting group 2
25-GRP3
BOOLEAN
Information number 25, activate setting group 3
26-GRP4
BOOLEAN
Information number 26, activate setting group 4
4.2.2.4
Settings
PID-3788-SETTINGS v5
Table 34:
I103IEDCMD Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
255
Function type (1-255)
Section 4
1MRK 511 394-UEN A
IEC 60870-5-103 vendor specific implementation
42
670 series 2.2 IEC
Communication protocol manual