Table 9:
I103MEASUSR supported indications
INF
FUN
GI
TYP
COT
Description
*
1)
*
2)
No, polled
with CL2
*
3)
2,7
Meas1
*
*
No, polled
with CL2
*
2,7
Meas2
*
*
No, polled
with CL2
*
2,7
Meas3
*
*
No, polled
with CL2
*
2,7
Meas4
*
*
No, polled
with CL2
*
2,7
Meas5
*
*
No, polled
with CL2
*
2,7
Meas6
*
*
No, polled
with CL2
*
2,7
Meas7
*
*
No, polled
with CL2
*
2,7
Meas8
*
*
No, polled
with CL2
*
2,7
Meas9
1) * User defined information value (PARAM.3)
2) * User defined information value (PARAM.2)
3) 9 = Measurands II, Format = Measurand II (7.3.1.8 in IEC 60870-5-103:1997), semantics per IE is
defined by semantics of connected source.
<Number of information elements> is defined by index of first input not connected.
Example: Input1, Input2, and Input4 are connected, Input3 is not connected.
<Number of information elements> will be 3 (Input3 NOT connected) -1 = 2, that
is, only Input1 and Input2 will be transmitted.
4.1.3
Function status auto-recloser for IEC 60870-5-103 I103AR
4.1.3.1
Functionality
GUID-7A132276-35A2-402C-9722-6259D65998F5 v1
I103AR is a function block with defined functions for autorecloser indications in
monitor direction. This block includes the
FunctionType
parameter, and the
information number parameter is defined for each output signal.
4.1.3.2
Function block
GUID-FAC5A3DF-73CB-4A39-A213-5C21ACA05756 v1
I103AR
BLOCK
16_ARACT
128_CBON
130_BLKD
IEC10000289-2-en.vsd
IEC10000289 V2 EN-US
Figure 7:
I103AR function block
Section 4
1MRK 511 394-UEN A
IEC 60870-5-103 vendor specific implementation
28
670 series 2.2 IEC
Communication protocol manual