4.1.1.2
Function block
GUID-EC5F1C83-0F47-4548-86E3-FFE056571241 v2
IEC10000287-1-en.vsd
I103MEAS
BLOCK
IL1
IL2
IL3
IN
UL1
UL2
UL3
UL1L2
UN
P
Q
F
IEC10000287 V1 EN-US
Figure 5:
I103MEAS function block
4.1.1.3
Signals
PID-6625-INPUTSIGNALS v4
Table 4:
I103MEAS Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of service value reporting
IL1
REAL
0.0
Service value for current phase L1
IL2
REAL
0.0
Service value for current phase L2
IL3
REAL
0.0
Service value for current phase L3
IN
REAL
0.0
Service value for residual current IN
UL1
REAL
0.0
Service value for voltage phase L1
UL2
REAL
0.0
Service value for voltage phase L2
UL3
REAL
0.0
Service value for voltage phase L3
UL1L2
REAL
0.0
Service value for voltage phase-phase L1-L2
UN
REAL
0.0
Service value for residual voltage UN
P
REAL
0.0
Service value for active power
Q
REAL
0.0
Service value for reactive power
F
REAL
0.0
Service value for system frequency
4.1.1.4
Settings
PID-6625-SETTINGS v4
Table 5:
I103MEAS Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
1
Function type (1-255)
MaxIL1
1 - 99999
A
1
3000
Maximum current phase L1
MaxIL2
1 - 99999
A
1
3000
Maximum current phase L2
MaxIL3
1 - 99999
A
1
3000
Maximum current phase L3
Table continues on next page
Section 4
1MRK 511 394-UEN A
IEC 60870-5-103 vendor specific implementation
24
670 series 2.2 IEC
Communication protocol manual