ABB IEC 60870-5-103 Скачать руководство пользователя страница 26

IEDTimeSkew

. But in 

LinMastTime

 it applies the time changes occurred

between two synchronization messages.

IEDTimeSkew

: The IED measures the offset in between its own time and

the master time and applies the same offset for the messages sent.

EvalTimeAccuracy

 evaluates time accuracy for invalid time. Specifies the

accuracy of the synchronization (5, 10, 20 or 40 ms). If the accuracy is less
than the specified value, the “Bad Time” flag is raised. To accommodate those
masters that are really bad in time sync, the 

EvalTimeAccuracy

 can be set to

Off

.

If IEC-103 is time-sync master and no IEC-103 time-sync is received within 23
hours then time-sync is considered lost and the no-sync flag will be raised. Other
protocols used for time-sync will have other criteria for lost-sync. IEC-103 will
report bad time if sync lost regardless of sync protocol.

3.2.2 

Settings

PID-6611-SETTINGS v5

Table 2:

RS485103 Non group settings (basic)

Name

Values (Range)

Unit

Step

Default

Description

SlaveAddress

1 - 254

-

1

1

Slave address

BaudRate

9600 Bd

19200 Bd

-

-

9600 Bd

Baudrate on serial line

CycMeasRepTime

1.0 - 1800.0

s

0.1

5.0

Cyclic reporting time of measurments

MasterTimeDomain

UTC

Local without DST

Local with DST

-

-

UTC

Master time domain

TimeSyncMode

IEDTime

LinMastTime

IEDTimeSkew

-

-

IEDTime

Time synchronization mode

EvalTimeAccuracy

Off

5ms

10ms

20ms

40ms

-

-

5ms

Evaluate time accuracy for invalid time

EventRepMode

SeqOfEvent

HiPriSpont

-

-

SeqOfEvent

Event reporting mode

CmdMode

MultiCmd

SingleCmd

-

-

SingleCmd

Command handling mode

RepIntermediatePos

Off

On

-

-

On

Report intermediate position

Section 3

1MRK 511 394-UEN A

IEC 60870-5-103 communication engineering

20

670 series 2.2 IEC

Communication protocol manual

Содержание IEC 60870-5-103

Страница 1: ...RELION 670 SERIES IEC 60870 5 103 670 series Version 2 2 Communication protocol manual ...

Страница 2: ......

Страница 3: ...Document ID 1MRK 511 394 UEN Issued October 2017 Revision A Product version 2 2 1 Copyright 2017 ABB All rights reserved ...

Страница 4: ...erms of such license This product includes software developed by the OpenSSL Project for use in the OpenSSL Toolkit http www openssl org This product includes cryptographic software written developed by Eric Young eay cryptsoft com and Tim Hudson tjh cryptsoft com Trademarks ABB and Relion are registered trademarks of the ABB Group All other brand or product names mentioned in this document may be...

Страница 5: ...product failure would create a risk for harm to property or persons including but not limited to personal injuries or death shall be the sole responsibility of the person or entity applying the equipment and those so responsible are hereby requested to ensure that all measures are taken to exclude or mitigate such risks This document has been carefully checked by ABB but deviations cannot be compl...

Страница 6: ...nd concerning electrical equipment for use within specified voltage limits Low voltage directive 2006 95 EC This conformity is the result of tests conducted by ABB in accordance with the product standard EN 60255 26 for the EMC directive and with the product standards EN 60255 1 and EN 60255 27 for the low voltage directive The product is designed in accordance with the international standards of ...

Страница 7: ...S485 and optical serial communication 17 IEC 60870 5 103 time synchronization 19 Settings 20 Section 4 IEC 60870 5 103 vendor specific implementation 23 Signals in monitoring direction 23 Measurands for IEC 60870 5 103 I103MEAS 23 Functionality 23 Function block 24 Signals 24 Settings 24 Supported information types 25 Measurands user defined signals for IEC 60870 5 103 I103MEASUSR 26 Functionality...

Страница 8: ...Supported information types 35 Supervison status for IEC 60870 5 103 I103SUPERV 35 Functionality 35 Function block 36 Signals 36 Settings 36 Supported information types 36 Status for user defined signals for IEC 60870 5 103 I103USRDEF 37 Functionality 37 Function block 37 Signals 38 Settings 38 Supported information types 40 Commands in control direction 40 Function commands for IEC 60870 5 103 I1...

Страница 9: ...CMD 46 Functionality 46 Function block 47 Signals 47 Settings 47 Supported information types 47 IED commands with position for IEC 60870 5 103 I103POSCMDV 48 Functionality 48 Function block 49 Signals 49 Settings 49 Supported information types 49 Disturbance recorder file transfer 50 Disturbance recordings 50 Disturbance recordings 50 Disturbance Recordings 50 Section 5 Interoperability 55 Physica...

Страница 10: ...in monitor direction 58 Auto reclosure indications in monitor direction 59 Measurands in monitor direction 59 Generic functions in monitor direction 59 Selection of standard information numbers in control direction 59 System functions in control direction 59 General commands in control direction 60 Generic functions in control direction 60 Basic application functions 60 Miscellaneous 61 Section 6 ...

Страница 11: ...E4F CC762FE28A3A v11 This manual is intended for the communication system engineer or system integrator responsible for pre engineering and engineering the communication setup in a substation from an IED perspective The system engineer or system integrator must have a basic knowledge of communication in protection and control systems and thorough knowledge of the specific communication protocol 1M...

Страница 12: ...o the project structure The manual also recommends a sequence for the engineering of protection and control functions LHMI functions as well as communication engineering for IEC 60870 5 103 IEC 61850 DNP3 LON and SPA The installation manual contains instructions on how to install the IED The manual provides procedures for mechanical and electrical installation The chapters are organized in the chr...

Страница 13: ...ls setting parameters and technical data sorted per function The manual can be used as a technical reference during the engineering phase installation and commissioning phase and during normal service The communication protocol manual describes the communication protocols supported by the IED The manual concentrates on the vendor specific implementations The point list manual describes the outlook...

Страница 14: ...ED670 Document numbers Application manual 1MRK 505 376 UEN Commissioning manual 1MRK 505 378 UEN Product guide 1MRK 505 379 BEN Technical manual 1MRK 505 377 UEN Type test certificate 1MRK 505 379 TEN Documents related to REG670 Document numbers Application manual 1MRK 502 071 UEN Commissioning manual 1MRK 502 073 UEN Product guide 1MRK 502 074 BEN Technical manual 1MRK 502 072 UEN Type test certi...

Страница 15: ...e test certificate 1MRK 506 378 TEN 670 series manuals Document numbers Operation manual 1MRK 500 127 UEN Engineering manual 1MRK 511 398 UEN Installation manual 1MRK 514 026 UEN Communication protocol manual DNP3 1MRK 511 391 UUS Communication protocol manual IEC 60870 5 103 1MRK 511 394 UEN Communication protocol manual IEC 61850 Edition 2 1MRK 511 393 UEN Communication protocol manual LON 1MRK ...

Страница 16: ...he tip icon indicates advice on for example how to design your project or how to use a certain function Although warning hazards are related to personal injury it is necessary to understand that under certain operational conditions operation of damaged equipment may result in degraded process performance leading to personal injury or death It is important that the user fully complies with all warn...

Страница 17: ...iguration to achieve a valid application configuration Logic diagrams describe the signal logic inside the function block and are bordered by dashed lines Signals in frames with a shaded area on their right hand side represent setting parameter signals that are only settable via the PST ECT or LHMI If an internal signal path cannot be drawn with a continuous line the suffix int is added to the sig...

Страница 18: ...12 ...

Страница 19: ...scription 5 1 Transmission frame formats 5 2 Link transmission procedures 5 3 General structure of application data 5 4 Definition and coding of application information elements 5 5 Basic application functions 5 6 Conformance testing guidelines 5 103 Companion standard for the informative interface of protection equipment The IEC 60870 5 1 6 parts are also used in communication protocols like IEC ...

Страница 20: ...to private function types and information numbers General principle of the mapping is to keep all process data belonging to the same function design inside the same IEC 60870 5 103 function type definition However if this default mapping principle causes interoperability problems with older installations the user can freely remap every available IEC 60870 5 103 process data point by using PCM600 M...

Страница 21: ...to the Communication and processing module the only hardware needed is optical fibres and an opto electrical converter for the PC RTU or a RS 485 connection depending on the used IED communication interface 1MRK 511 394 UEN A Section 2 IEC 60870 5 103 overview 670 series 2 2 IEC 15 Communication protocol manual ...

Страница 22: ...16 ...

Страница 23: ...mation number must be supplied for each IEC 60870 5 103 function block instance in the Parameter Setting tool 4 Set the general communication settings for IEC 60870 5 103 and time synchronization parameters in the Parameter Setting tool 3 2 Settings for RS485 and optical serial communication M17109 118 v12 General settings IEC 60870 5 103 can be configured to operate on the SLM optical serial port...

Страница 24: ...aveAddress and BaudRate Settings for slave number and communication speed baud rate The slave number can be set to any value between 1 and 254 The communication speed can be set either to 9600 bits s or 19200 bits s RevPolarity Setting for inverting the light or not Standard IEC 60870 5 103 setting is On CycMeasRepTime See I103MEAS function block for more information EventRepMode Defines the mode ...

Страница 25: ...PST Only CoarseSyncSrc can be set to 103 not FineSyncSource After setting up the time synchronization source the user must check and modify the IEC 60870 5 103 time synchronization specific settings under Main menu Configuration Communication Station communication IEC60870 5 103 MasterTimeDomain specifies the domain of time sync sent by the master It also defines the domain in which time stamps ar...

Страница 26: ...other criteria for lost sync IEC 103 will report bad time if sync lost regardless of sync protocol 3 2 2 Settings PID 6611 SETTINGS v5 Table 2 RS485103 Non group settings basic Name Values Range Unit Step Default Description SlaveAddress 1 254 1 1 Slave address BaudRate 9600 Bd 19200 Bd 9600 Bd Baudrate on serial line CycMeasRepTime 1 0 1800 0 s 0 1 5 0 Cyclic reporting time of measurments MasterT...

Страница 27: ...ain UTC Local without DST Local with DST UTC Master time domain TimeSyncMode IEDTime LinMastTime IEDTimeSkew IEDTime Time synchronization mode EvalTimeAccuracy Off 5ms 10ms 20ms 40ms 5ms Evaluate time accuracy for invalid time EventRepMode SeqOfEvent HiPriSpont SeqOfEvent Event reporting mode CmdMode MultiCmd SingleCmd SingleCmd Command handling mode RepIntermediatePos Off On On Report intermediat...

Страница 28: ...22 ...

Страница 29: ...6F220 v3 103MEAS is a function block that reports all valid measuring types depending on connected signals The set of connected input will control which ASDUs Application Service Data Units are generated 9 Will be generated if at least IL1 is connected IL2 IL3 UL1 UL2 UL3 P Q F are optional but there can be no holes 3 4 Will be generated if IN and UN are present 3 3 Will be generated if IL2 Ul1L2 ...

Страница 30: ... 0 0 Service value for voltage phase L2 UL3 REAL 0 0 Service value for voltage phase L3 UL1L2 REAL 0 0 Service value for voltage phase phase L1 L2 UN REAL 0 0 Service value for residual voltage UN P REAL 0 0 Service value for active power Q REAL 0 0 Service value for reactive power F REAL 0 0 Service value for system frequency 4 1 1 4 Settings PID 6625 SETTINGS v4 Table 5 I103MEAS Non group settin...

Страница 31: ...r limit for measured voltages and frequency is 1 2 times rated value The upper limit is the maximum value that can be encoded into the ASDU Application Service Data Unit Any value higher than this value will be tagged as OVERFLOW The factors 1 2 and 2 4 are taken from the 103 standard and require that a rated value to use as base exists and then use 1 2 or 2 4 times rated as maxVal You can use 2 4...

Страница 32: ...0588CB v1 IEC10000288 1 en vsd I103MEASUSR BLOCK INPUT1 INPUT2 INPUT3 INPUT4 INPUT5 INPUT6 INPUT7 INPUT8 INPUT9 IEC10000288 V1 EN US Figure 6 I103MEASUSR function block 4 1 2 3 Signals PID 3791 INPUTSIGNALS v5 Table 7 I103MEASUSR Input signals Name Type Default Description BLOCK BOOLEAN 0 Block of service value reporting INPUT1 REAL 0 0 Service value for measurement on input 1 INPUT2 REAL 0 0 Serv...

Страница 33: ... 00 Maximum value for measurement on input 3 MaxMeasur4 0 05 10000000000 00 0 05 1000 00 Maximum value for measurement on input 4 MaxMeasur5 0 05 10000000000 00 0 05 1000 00 Maximum value for measurement on input 5 MaxMeasur6 0 05 10000000000 00 0 05 1000 00 Maximum value for measurement on input 6 MaxMeasur7 0 05 10000000000 00 0 05 1000 00 Maximum value for measurement on input 7 MaxMeasur8 0 05...

Страница 34: ...le Input1 Input2 and Input4 are connected Input3 is not connected Number of information elements will be 3 Input3 NOT connected 1 2 that is only Input1 and Input2 will be transmitted 4 1 3 Function status auto recloser for IEC 60870 5 103 I103AR 4 1 3 1 Functionality GUID 7A132276 35A2 402C 9722 6259D65998F5 v1 I103AR is a function block with defined functions for autorecloser indications in monit...

Страница 35: ...k for autorecloser in monitor direction with defined functions Number of instances 1 Function type is selected with parameter FunctionType Information number is defined for each output signal Table 12 I103AR supported indications INF Description 16 Autorecloser active 128 CB on by Autorecloser 130 Autorecloser blocked 4 1 4 Function status earth fault for IEC 60870 5 103 I103EF GUID F23B392E B55D ...

Страница 36: ...v5 Table 14 I103EF Non group settings basic Name Values Range Unit Step Default Description FunctionType 1 255 1 160 Function type 1 255 4 1 4 5 Supported information types Earth fault indications in monitor direction I103EF M11874 199 v8 Indication block for earth fault in monitor direction with defined functions Number of instances 1 Function type is selected with parameter FunctionType Informat...

Страница 37: ... the protocol is the time difference in between the signal that is triggering the Disturbance Recorder and the respective configured signal to the IEC 60870 5 103 I103FLTPROT 4 1 5 2 Function block GUID F0ED13B8 6B82 4CA7 8F22 C200C33EBB7E v2 I103FLTPROT BLOCK 64_STL1 65_STL2 66_STL3 67_STIN 68_TRGEN 69_TRL1 70_TRL2 71_TRL3 72_TRBKUP 73_SCL 74_FW 75_REV 76_TRANS 77_RECEV 78_ZONE1 79_ZONE2 80_ZONE3...

Страница 38: ...LEAN 0 Information number 77 signal received 78_ZONE1 BOOLEAN 0 Information number 78 zone 1 79_ZONE2 BOOLEAN 0 Information number 79 zone 2 80_ZONE3 BOOLEAN 0 Information number 80 zone 3 81_ZONE4 BOOLEAN 0 Information number 81 zone 4 82_ZONE5 BOOLEAN 0 Information number 82 zone 5 83_ZONE6 BOOLEAN 0 Information number 83 zone 6 84_STGEN BOOLEAN 0 Information number 84 start general 85_BFP BOOLE...

Страница 39: ...ype is selected with parameter FunctionType Information number is defined for each input signal Table 18 I103FLTPROT supported functions INF Description TYP GI COT 64 Start phase L1 2 Y 1 7 9 65 Start phase L2 2 Y 1 7 9 66 Start phase L3 2 Y 1 7 9 67 Start residual current IN 2 Y 1 7 9 68 Trip general 2 N 1 7 69 Trip phase L1 2 N 1 7 70 Trip phase L2 2 N 1 7 71 Trip phase L3 2 N 1 7 72 Back up tri...

Страница 40: ... monitor direction This block uses parameter as FunctionType and information number parameter is defined for each input signal 4 1 6 2 Function block GUID 421D5C37 27A5 476A A7D9 40E70AFDFDC8 v1 I103IED BLOCK 19_LEDRS 21_TESTM 22_SETCH 23_GRP1 24_GRP2 25_GRP3 26_GRP4 IEC10000292 2 en vsd IEC10000292 V2 EN US Figure 10 I103IED function block 4 1 6 3 Signals PID 3975 INPUTSIGNALS v5 Table 19 I103IED...

Страница 41: ...efined IED functions Number of instances 1 Function type is selected with parameter FunctionType Information number is defined for each input signals Table 21 I103IED supported functions INF Description 19 LED reset 21 TestMode 22 Local Parameter setting 23 Setting group 1 active 24 Setting group 2 active 25 Setting group 3 active 26 Setting group 4 active 4 1 7 Supervison status for IEC 60870 5 1...

Страница 42: ...38_VTFF BOOLEAN 0 Information number 38 fuse failure VT 46_GRWA BOOLEAN 0 Information number 46 group warning 47_GRAL BOOLEAN 0 Information number 47 group alarm 4 1 7 4 Settings PID 3976 SETTINGS v5 Table 23 I103SUPERV Non group settings basic Name Values Range Unit Step Default Description FunctionType 1 255 1 1 Function type 1 255 4 1 7 5 Supported information types Supervision indications in m...

Страница 43: ...tance is associated with a Function Type FUN and each input signal with an Information Number INF Additionally all input signals may be defined to use relative time and how to respond to a GI request The user is responsible for assigning a proper FUN value and proper INF values to all connected inputs See Settings for details 4 1 8 2 Function block GUID B8312E77 514D 4117 BB31 B9907755580C v1 I103...

Страница 44: ... Relative The maximum relative time and unit conform to the IEC 60870 5 103 standard 4 1 8 4 Settings PID 6485 SETTINGS v5 Table 26 I103USRDEF Non group settings basic Name Values Range Unit Step Default Description FunctionType 1 255 1 5 Function type 1 255 InfNo1 1 255 1 1 Information number for binary input 1 1 255 InfNo2 1 255 1 2 Information number for binary input 2 1 255 InfNo3 1 255 1 3 In...

Страница 45: ...Included Response and status change GI GiNo7 Excluded Included Included Response and status change GI GiNo8 Excluded Included Included Response and status change GI GUID 86DE9DBA BE2F 4CC9 B447 1D2D86849EFF v2 The FunctionType parameter associates a particular instance of the function block with a FUN Refer to the IEC 60870 5 103 standard for details The InfNon parameters are used to associate eac...

Страница 46: ...Input signal 06 x 1 2 1 7 9 7 Input signal 07 x 1 2 1 7 9 8 Input signal 08 x 1 2 1 7 9 1 User defined information number 4 2 Commands in control direction M11874 27 v1 4 2 1 Function commands for IEC 60870 5 103 I103CMD 4 2 1 1 Functionality GUID 973929FE 292B 42A5 ACF9 BC95E2B16AE1 v2 I103CMD is a command function block in control direction with pre defined output signals The signals are in stea...

Страница 47: ...ngs basic Name Values Range Unit Step Default Description FunctionType 1 255 1 1 Function type 1 255 4 2 1 5 Supported information types Function commands in control direction pre defined I103CMD M11874 53 v6 Function command block in control direction with defined output signals Number of instances 1 Function type is selected with parameter FunctionType Information number is defined for each outp...

Страница 48: ... Name Type Default Description BLOCK BOOLEAN 0 Block of commands PID 3788 OUTPUTSIGNALS v5 Table 33 I103IEDCMD Output signals Name Type Description 19 LEDRS BOOLEAN Information number 19 reset LEDs 23 GRP1 BOOLEAN Information number 23 activate setting group 1 24 GRP2 BOOLEAN Information number 24 activate setting group 2 25 GRP3 BOOLEAN Information number 25 activate setting group 3 26 GRP4 BOOLE...

Страница 49: ...EAC8 20BE 46EE 93FE C70188D0BC89 v1 I103USRCMD is a command block in control direction with user defined output signals These function blocks include the FunctionType parameter for each block in the private range and the Information number parameter for each output signal 4 2 3 2 Function block GUID 5EBEAED5 ABD9 4257 B879 DF7FD9F7805A v1 IEC10000284 1 en vsd I103USRCMD BLOCK OUTPUT1 OUTPUT2 OUTPU...

Страница 50: ...rmation number for output 2 1 255 InfNo_3 1 255 1 3 Information number for output 3 1 255 InfNo_4 1 255 1 4 Information number for output 4 1 255 InfNo_5 1 255 1 5 Information number for output 5 1 255 InfNo_6 1 255 1 6 Information number for output 6 1 255 InfNo_7 1 255 1 7 Information number for output 7 1 255 InfNo_8 1 255 1 8 Information number for output 8 1 255 4 2 3 5 Supported information ...

Страница 51: ... pulsed ON OFF or 2 steady ON OFF outputs The ON output is pulsed with a command with value 2 while the OFF output is pulsed with a command value 1 If in steady mode is ON asserted and OFF deasserted with command 2 and vice versa with command 1 Steady mode is selected by setting PulseLength 0 The I103GENCMD is retained and a command in steady mode will be reissued on restart 4 2 4 2 Function block...

Страница 52: ... 5 1 Functionality GUID 1E40B94D B6A6 42F0 8757 A47B8A3FA3CD v7 I103POSCMD is a transceiver function that monitors activity on its input signals and interprets any state transition into commands then sent over an established IEC 60870 5 103 link Additionally it listens for general interrogation GI requests and replies to those with a GI response message with the current state of each connected inp...

Страница 53: ...able 43 I103POSCMD Input signals Name Type Default Description BLOCK BOOLEAN 0 Block of status reporting POSITION INTEGER 0 Position of controllable object SELECT BOOLEAN 0 Select of controllable object 4 2 5 4 Settings PID 6997 SETTINGS v1 Table 44 I103POSCMD Non group settings basic Name Values Range Unit Step Default Description FunctionType 1 255 1 1 Function type InfNo 160 236 4 160 Informati...

Страница 54: ...and replies to those with a GI response message with the current state of each connected input Input POSITION is a double indication signal and it is GI enabled This means that any state transition that is to ON OFF intermediate and faulty is reported spontaneously However the intermediate and faulty states may be suppressed by setting the Report Intermediate Position Off See the settings for RS48...

Страница 55: ...Type 1 255 1 1 Function type InfNo 160 209 1 160 Information number for command output 4 2 6 5 Supported information types IED commands with position for IEC 60870 5 103 I103POSCMDV GUID EDA379DC 73E7 48C5 AC3B A6CA969F351F v2 Number of instances 50 The function type for each function block instance is selected with the parameter FunctionType The information number must be selected for the command...

Страница 56: ... Application Service Data Units defined in the standard Analog signals 40 channels the channel number for each channel has to be specified Channels used in the public range are 1 to 8 and with IL1 connected to channel 1 on disturbance function block A1RADR IL2 connected to channel 2 on disturbance function block A1RADR IL3 connected to channel 3 on disturbance function block A1RADR IN connected to...

Страница 57: ...Table 49 Table 49 Channels on disturbance recorder sent with a given ACC DRA Input ACC IEC 60870 5 103 meaning 1 1 IL1 2 2 IL2 3 3 IL3 4 4 IN 5 5 UL1 6 6 UL2 7 7 UL3 8 8 UN 9 64 Private range 10 65 Private range 11 66 Private range 12 67 Private range 13 68 Private range 14 69 Private range 15 70 Private range 16 71 Private range 17 72 Private range 18 73 Private range 19 74 Private range 20 75 Pr...

Страница 58: ...hen a disturbance is deleted by other client for example SPA or when a new disturbance has been recorded or when the master has uploaded a disturbance Deviations from the standard Information sent in the disturbance upload is specified by the standard however some of the information are adapted to information available in disturbance recorder in the IED series This section describes all data that ...

Страница 59: ...o disturbance number which is incremented for each disturbance ASDU26 ASDU31 When a disturbance has been selected by the master by sending ASDU24 the protection equipment answers by sending ASDU26 which contains an information element named NOF number of grid faults This number must indicate fault number in the power system that is a fault in the power system with several trip and auto reclosing h...

Страница 60: ...54 ...

Страница 61: ...A68 v2 Table 51 Optical interface Supported Glass fibre Yes Plastic fibre Yes F SMA type connector No BFOC 2 5 type connector Yes HFBR snap in type connector Yes 5 1 3 Transmission speed GUID 0B5E31F3 7EC4 401D B86C FBE19622ECF7 v2 Table 52 Transmission speed Supported 9 600 bit s Yes 19 200 bit s Yes 5 2 Link layer GUID 56EEBF6D 2181 41AF AC39 8132B54C6627 v1 There are no choices for the link lay...

Страница 62: ...on 5 3 3 1 System functions in monitor direction GUID 99E09728 48CD 4C67 97B5 73F564893E73 v2 Table 54 System functions in monitor direction INF Semantics Supported 0 End of general interrogation Yes 0 Time synchronization Yes 2 Reset FCB Yes 3 Reset CU Yes 4 Start restart Yes 5 Power on Yes 5 3 3 2 Status indications in monitor direction GUID D1C20715 AC82 4FAB B5AA 0E4A439C4129 v3 Table 55 Statu...

Страница 63: ...3 Measurand supervision U Yes 35 Phase sequence supervision No 36 Trip circuit supervision No 37 I back up operation Yes 38 VT fuse failure Yes 39 Teleprotection disturbed No 46 Group warning Yes 47 Group alarm Yes 5 3 3 4 Earth fault indications in monitor direction GUID 204F36F6 A9E6 4B74 9AE3 7FE2041ADC7F v3 Table 57 Earth fault indications in monitor direction INF Semantics Supported 48 Earth ...

Страница 64: ...tion X in ohms Yes 74 Fault forward line Yes 75 Fault reverse busbar Yes 76 Teleprotection signal transmitted Yes 77 Teleprotection signal received Yes 78 Zone 1 Yes 79 Zone 2 Yes 80 Zone 3 Yes 81 Zone 4 Yes 82 Zone 5 Yes 83 Zone 6 Yes 84 General start pick up Yes 85 Breaker failure Yes 86 Trip measuring system L1 Yes 87 Trip measuring system L2 Yes 88 Trip measuring system L3 Yes 89 Trip measurin...

Страница 65: ...DDE3D v2 Table 61 Generic functions in monitor direction INF Semantics Supported 240 Read headings of all defined groups No 241 Read values or attributes of all entries of one group No 243 Read directory of a single entry No 244 Read value or attribute of a single entry No 245 End of general interrogation of generic data No 249 Write entry with confirmation No 250 Write entry with execution No 251...

Страница 66: ...trol direction INF Semantics Supported 240 Read headings of all defined groups No 241 Read values or attributes of all entries of one group No 243 Read directory of a single entry No 244 Read value or attribute of a single entry No 245 General interrogation of generic data No 248 Write entry No 249 Write entry with confirmation No 250 Write entry with execution No 251 Write entry abort No 5 3 5 Ba...

Страница 67: ...e used in ASDU 3 and ASDU 9 i e for each measurand there is only one choice Table 66 Miscellaneous Measurand Max MVAL rated value times 1 2 2 4 Current L1 No Yes Current L2 No Yes Current L3 No Yes Voltage L1 E Yes No Voltage L2 E Yes No Voltage L3 E Yes No Active power P No Yes Reactive power Q No Yes Frequency f Yes No Voltage L1 L2 Yes No 1MRK 511 394 UEN A Section 5 Interoperability 670 series...

Страница 68: ...62 ...

Страница 69: ...Application service data unit AWG American Wire Gauge standard BBP Busbar protection BFOC 2 5 Bayonet fibre optic connector BFP Breaker failure protection BI Binary input BIM Binary input module BOM Binary output module BOS Binary outputs status BR External bistable relay BS British Standards BSR Binary signal transfer function receiver blocks BST Binary signal transfer function transmit blocks C3...

Страница 70: ...Common Format for Transient Data Exchange format for Disturbance recorder according to IEEE ANSI C37 111 1999 IEC 60255 24 Contra directional Way of transmitting G 703 over a balanced line Involves four twisted pairs two of which are used for transmitting data in both directions and two for transmitting clock signals COT Cause of transmission CPU Central processing unit CR Carrier receive CRC Cycl...

Страница 71: ...lectromagnetic interference EnFP End fault protection EPA Enhanced performance architecture ESD Electrostatic discharge F SMA Type of optical fibre connector FAN Fault number FCB Flow control bit Frame count bit FOX 20 Modular 20 channel telecommunication system for speech data and protection signals FOX 512 515 Access multiplexer FOX 6Plus Compact time division multiplexer for the transmission of...

Страница 72: ...Requirements for protective current transformers for transient performance IEC 60870 5 103 Communication standard for protection equipment A serial master slave protocol for point to point communication IEC 61850 Substation automation communication standard IEC 61850 8 1 Communication protocol standard IEEE Institute of Electrical and Electronics Engineers IEEE 802 12 A network technology standard...

Страница 73: ...acket switching protocol It provides packet routing fragmentation and reassembly through the data link layer 2 Ingression protection according to IEC 60529 IP 20 Ingression protection according to IEC 60529 level 20 IP 40 Ingression protection according to IEC 60529 level 40 IP 54 Ingression protection according to IEC 60529 level 54 IRF Internal failure signal IRIG B InterRange Instrumentation Gr...

Страница 74: ...ult but perhaps it should not have seen it PCI Peripheral component interconnect a local data bus PCM Pulse code modulation PCM600 Protection and control IED manager PC MIP Mezzanine card standard PMC PCI Mezzanine card POR Permissive overreach POTT Permissive overreach transfer trip Process bus Bus or LAN used at the process level that is in near proximity to the measured and or controlled compon...

Страница 75: ...A threaded connector with constant impedance SMT Signal matrix tool within PCM600 SMS Station monitoring system SNTP Simple network time protocol is used to synchronize computer clocks on local area networks This reduces the requirement to have accurate hardware clocks in every embedded system in a network Each embedded node can instead synchronize with a remote clock providing the required accura...

Страница 76: ...UMT User management tool Underreach A term used to describe how the relay behaves during a fault condition For example a distance relay is underreaching when the impedance presented to it is greater than the apparent impedance to the fault applied to the balance point that is the set reach The relay does not see the fault but perhaps it should have seen it See also Overreach UTC Coordinated Univer...

Страница 77: ...ing interface primarily used for telecom equipment 3IO Three times zero sequence current Often referred to as the residual or the earth fault current 3UO Three times the zero sequence voltage Often referred to as the residual voltage or the neutral point voltage 1MRK 511 394 UEN A Section 6 Glossary 670 series 2 2 IEC 71 Communication protocol manual ...

Страница 78: ...72 ...

Страница 79: ...73 ...

Страница 80: ... AB Grid Automation Products 721 59 Västerås Sweden Phone 46 0 21 32 50 00 abb com protection control Copyright 2017 ABB All rights reserved Specifications subject to change without notice 1MRK 511 394 UEN ...

Отзывы: