ABB i-bus® KNX
PARAMETERS
7.4.31
Operating mode after exceeding monitoring time
This parameter is used to define which operating mode is activated if no value is received on group ob-
ject
Operating mode normal (master)
during the specified period. This operating mode remains active
until a new value is received on group object
Operating mode normal (master)
Option
Building Protection
Comfort
Standby
Economy
Prerequisites for visibility
\ Option
Controller channel
– Parameter
Option
Activated
– Parameter
Monitor receipt of group object "Operating mode normal (master)"
Option
Activated
• The parameter is in the parameter window
7.4.32
Operating mode after bus voltage recovery or ETS download
This parameter is used to define which operating mode is activated after bus voltage recovery or ETS
download. The operating mode remains active until a new operating mode is set.
Note
After an ETS reset the
Comfort
operating mode is always set.
Note
The operating mode should be defined during the planning phase. If the operating mode is defined in-
correctly, this might reduce comfort or increase energy consumption.
For an explanation of the individual operating modes →
Explanation of the operating modes, Page 174
Option
Comfort
Standby
Economy
Building Protection
As before bus voltage failure/download
Prerequisites for visibility
\ Option
Controller channel
• The parameter is in the parameter window
Product manual | EN-US | VC/S 4.x.1 | 2CDC508220D0211 Rev. B
73