ABB i-bus® KNX
PARAMETERS
7.4.11
Number of group objects Actual temperature
This parameter is used to define the number of group objects via which an actual temperature value is
received via the bus (
ABB i-bus® KNX
).
Option
1
The actual temperature is received via one group object.
The following dependent group objects are displayed:
•
2
The actual temperature is received via two group objects. The received values are weighted.
The following dependent parameters are shown:
•
Weighting of external measurement 2
The following dependent group objects are displayed:
•
•
Prerequisites for visibility
– Parameter
\
Option
Controller channel
– Parameter
\
Options
Via group object / Via phys. device input or group
object
• The parameter is in the parameter window
.
7.4.12
Limit number of telegrams
This parameter is used to define whether the number of telegrams sent by the device will be limited. The
fewer telegrams sent, the lower the bus load will be.
More information: →
Telegram rate limit, Page 189
.
Option
No
The number of telegrams is not limited.
Yes
The following dependent parameters are shown:
•
•
Prerequisites for visibility
• The parameter is in the parameter window
.
Product manual | EN-US | VC/S 4.x.1 | 2CDC508220D0211 Rev. B
61
Note about navigation in the PDF: Key combination 'Alt + left arrow'
jumps to the previous view/page