FCA/S 1.x.x.1 | 2CDC508134D0202 65
3
Commissioning
3.1
Overview
The application
Fan Coil Actuator PWM/2
is available for the Fan Coil Actuator FCA/S 1.1.1.2.
The application
Fan Coil Actuator 0-10V/2
is available for the Fan Coil Actuator FCA/S 1.2.1.2.
The application
Fan Coil Actuator PWM M/2
is available for the Fan Coil Actuator FCA/S 1.1.2.2.
The application
Fan Coil Actuator 0-10V M2
is available for the Fan Coil Actuator FCA/S 1.2.2.2.
Programming requires the ETS.
For use of the i-bus
®
Tool, see:
The following functions are available:
Additional output
For control of auxiliary electrical heating, e.g. in the winter
summer transition
phase.
Fan
A three-speed fan is controlled alternately with a two-way connection or with speed
switching.
FCA/S 1.1.x.2: electronic
Valve drives are controlled. Control occurs via PWM or 3-point. The outputs are
protected against short circuit.
FCA/S 1.2.x.2: analog
Valve drives are controlled. Control occurs via an analog control signal of 0...10 V.
The outputs are protected against short circuit.
Inputs
There are four inputs available. These are used to monitor or connect the window
contact, condensation (dew point), detectors or temperature sensors, for example.
The 6 A outputs are available for Fan Coil applications.
Attention
Improper switching will destroy the fan motors.
Follow the technical data for the fan, e.g. speed or switching function.
For further information see:
Parameter window E, F, G: Fan (Multi-level)
The Fan Coil Actuator features a relay in each output, which is mechanically independent of the other
outputs. Switching noises cannot be avoided due to the mechanical nature of the design.
The installation location of the Fan Coil Actuator can either be centrally in an electrical distribution board,
or distributed in a Fan Coil unit. Usually, the Fan Coil Actuator is used in conjunction with a room
thermostat for an individual room temperature control system. The room thermostat sends a control
variable which is used to control the fan stages via the Fan Coil Actuator.
Fan Coil controls
Fan with three fan speeds
With changeover or step control
1 control value/1 valve
2 control values/1 valve
2 control values/1 valve/ with switching object
2 control values/2 valves
2 control values/2 valves/
with switching object
For further information, see:
Содержание i-bus KNX
Страница 1: ...ABB i bus KNX Fan Coil Actuators FCA S Product Manual ...
Страница 2: ......
Страница 6: ......
Страница 12: ......
Страница 24: ...ABB i bus KNX Device technology 22 2CDC508134D0202 FCA S 1 x x 1 2 1 12 Dimension drawing 2CDC072016F0013 ...
Страница 36: ...ABB i bus KNX Device technology 34 2CDC508134D0202 FCA S 1 x x 1 2 2 12 Dimension drawing 2CDC072031F0011 ...
Страница 48: ...ABB i bus KNX Device technology 46 2CDC508134D0202 FCA S 1 x x 1 2 3 11 Dimension drawing 2CDC072015F0013 ...
Страница 60: ...ABB i bus KNX Device technology 58 2CDC508134D0202 FCA S 1 x x 1 2 4 11 Dimension drawing 2CDC072015F0012 ...
Страница 262: ...ABB i bus KNX Appendix 260 2CDC508134D0202 FCA S 1 x x 1 A 6 Notes ...
Страница 263: ......