ABB i-bus
®
KNX
Commissioning
FCA/S 1.x.x.1 | 2CDC508134D0202 173
3.2.4.2.1
Parameter
Distinction between long and short operation
– No
If the option
No
has been selected with the parameter
Distinction between long and short operation
, the
following parameters appear in
Opening the contact -> Event 0
Closing the contact -> Event 1
<
−−− NOTE
Activate minimum signal duration
Options:
No
Yes
Selection
Yes:
Dependent parameters:
On closing the contact
in [0...65,535] X 0.1 s
Options:
0…10…65,535
On opening the contact
in [0…65,535] x 0.1 s
Options:
0…10…65,535