3.2.3.20
Parameter window H: Output
All settings for output H are made in this parameter window.
This parameter window is visible if
Output H
Reaction of output
Options:
N/O
N/C
This parameter sets whether the output operates as a
normally closed contact
or
normally open contact
.
Normally opened contact
: An ON telegram (1) closes the contact, and an OFF telegram (0) opens the
contact.
Normally closed contact
: An ON telegram (1) opens the contact, and an OFF telegram (0) closes the
contact.
Contact position
on bus voltage failure
Options:
Unchanged
Open
Closed
The output can adopt a defined state on bus voltage failure (BVF) using this parameter.
Open:
The contact is opened with bus voltage failure.
Closed:
The contact is closed with bus voltage failure.
Unchanged:
No change of the contact setting.
Note
Take note of the reaction on bus voltage failure, recovery and download.
Содержание i-bus KNX
Страница 1: ...ABB i bus KNX Fan Coil Actuators FCA S Product Manual ...
Страница 2: ......
Страница 6: ......
Страница 12: ......
Страница 24: ...ABB i bus KNX Device technology 22 2CDC508134D0202 FCA S 1 x x 1 2 1 12 Dimension drawing 2CDC072016F0013 ...
Страница 36: ...ABB i bus KNX Device technology 34 2CDC508134D0202 FCA S 1 x x 1 2 2 12 Dimension drawing 2CDC072031F0011 ...
Страница 48: ...ABB i bus KNX Device technology 46 2CDC508134D0202 FCA S 1 x x 1 2 3 11 Dimension drawing 2CDC072015F0013 ...
Страница 60: ...ABB i bus KNX Device technology 58 2CDC508134D0202 FCA S 1 x x 1 2 4 11 Dimension drawing 2CDC072015F0012 ...
Страница 262: ...ABB i bus KNX Appendix 260 2CDC508134D0202 FCA S 1 x x 1 A 6 Notes ...
Страница 263: ......