ABB i-bus
®
KNX
Commissioning
154 2CDC508134D0202 | FCA/S 1.x.x.1
3.2.3.17
Parameter window Threshold (One-level)
The thresholds are defined in this parameter window.
Threshold value OFF <-> ON
in % [1...100]
Options:
1…10…100
This defines the threshold value at which switch on occurs. If the value in the control value communication
object is greater than or equal to the parameterized threshold value, it is switched on. If the value is less, it
is switched off.
Hysteresis is only taken into account in automatic operation
Note
Hysteresis threshold
value in % +/- [0...20 %]
Options:
0…5…20
This sets a hysteresis at which switchover to the next fan speed occurs.
The setting 0 causes immediate switching without hysteresis.
The entered percentage value is directly added to or subtracted from the percentage value of
Threshold
value speed x
. The result is a new upper or lower threshold value.
Switch threshold top (switch on) = threshold value + hysteresis
Switch threshold bottom (switch off) = threshold value - hysteresis
Содержание i-bus KNX
Страница 1: ...ABB i bus KNX Fan Coil Actuators FCA S Product Manual ...
Страница 2: ......
Страница 6: ......
Страница 12: ......
Страница 24: ...ABB i bus KNX Device technology 22 2CDC508134D0202 FCA S 1 x x 1 2 1 12 Dimension drawing 2CDC072016F0013 ...
Страница 36: ...ABB i bus KNX Device technology 34 2CDC508134D0202 FCA S 1 x x 1 2 2 12 Dimension drawing 2CDC072031F0011 ...
Страница 48: ...ABB i bus KNX Device technology 46 2CDC508134D0202 FCA S 1 x x 1 2 3 11 Dimension drawing 2CDC072015F0013 ...
Страница 60: ...ABB i bus KNX Device technology 58 2CDC508134D0202 FCA S 1 x x 1 2 4 11 Dimension drawing 2CDC072015F0012 ...
Страница 262: ...ABB i bus KNX Appendix 260 2CDC508134D0202 FCA S 1 x x 1 A 6 Notes ...
Страница 263: ......