ABB i-bus
®
KNX
Commissioning
© 2008 ABB STOTZ-KONTAKT GmbH
180
3.3.3.5
Communication objects
HVAC System
2 Control values/4 pipe
No.
Function
Object name
Data type
Flags
29
Control value HEATING
Control input
EIS 6, 1 byte
DPT 5.001
C, W
This communication object is enabled if in parameter window
Control input
the parameter
HVAC System
has been selected with the option
2 Control value/2 pipe
.
Using this communication object the control value HEATING is predefined as
a 1 byte % value.
Telegram value:
0 % = OFF, no heating
100 % = ON, largest control value, maximum heating
30
Control value COOLING
Control input
EIS 6, 1 byte
DPT 5.001
C, W
This communication object is enabled if in parameter window
Control input
the parameter
HVAC System
has been selected with the option
2 Control value/2 pipe
.
Using this communication object the control value COOLING is predefined as
a 1 byte % value.
Telegram value:
0 % = OFF, no cooling
100 % = ON, largest control value, maximum cooling
31
Not assigned.