3.3.2.2
Communication objects
Fan one-level
No.
Function
Object name
Data type
Flags
10
Not assigned.
11
Switch
Fan
EIS 1, 1 bit
DPT 1.001
C, W
This communication object is enabled if in parameter window L, M, N:
Fan (3 x 6 A)
the parameter
Fan type
has been selected with the option
one-level
.
With this 1 bit communication object the fan can be switched on or off.
Limitations through forced operation are retained Automatic operation is disabled. A renewed
activation occurs via the communication objects
Automatic ON/OFF.
If several ON commands with the value 1 are received, the value last received for the fan
control is decisive.
An OFF command switches the fan fully off.
Telegram value:
0 = fan OFF
1 = fan ON
12…
14
Not assigned.