Commissioning
© 2008 ABB STOTZ-KONTAKT GmbH
152
3.2.9
Parameter window
O, P: Valve HEATING
(0.5 A AC) –
Continuous, PWM
This parameter appears if the option
Continuous, PWM
has been selected in
the
Valve control
parameter.
Valve type
Options: de-energised
closed
de-energised
opened
Using this parameter the valve type for the connected valve is set.
How does a de-energised closed (normally closed) valve
behave?
If no current flows in the control circuit the valve is closed. The valve
is opened as soon as current flows in the control circuit.
How does a de-energised opened (normally open) valve behave?
If no current flows in the control circuit the valve is opened.
The valve is closed as soon as current flows in the control circuit.
•
de-energised closed:
The following parameter appears:
Valve position on bus voltage failure
Option: closed
This option is intended as a marker. The valve remains closed at
bus voltage failure.