ABB i-bus
®
KNX
Commissioning
© 2008 ABB STOTZ-KONTAKT GmbH
137
3.2.6.5.2 Parameter window
- Automatic operation
This parameter window is visible if in parameter window L, M, N:
Fan
(3 x 6 A)
the option
yes
has been selected in the
Enable automatic
operatio
n parameter.
In this parameter window the threshold values for switchover of the fan
speed are defined. Furthermore, the limitations can also be enabled.
The corresponding valve control communication object receives the value 1
if a fan speed is set. If a fan speed is not set the communication object will
receive the value 0.
Object value “Automatic ON/OFF”
switch on to the automatic
Options: 1
0
This parameter defines how to react to a telegram.
•
1:
Automatic is activated by a telegram with value 1.
•
0:
Automatic is activated by a telegram with value 0.
Threshold value OFF <-> ON
in % [1…100]
Options: 1…10…100
Here the threshold value at which switch on occurs is defined. If the value in
the control value communication object is greater than or equal to the
parameterised threshold value, it is switched on. If the value is less, then it is
switched off.