122
3.2.6.3.2 Parameter window
- Automatic operation
This parameter window is visible if in parameter window
L, M, N: Fan
(3 x 6 A)
the option
yes
has been selected in the
Enable automatic
operatio
n parameter.
In this parameter window the threshold values for switchover of the fan
speed are defined. Furthermore, the limitations can also be enabled.
Important
The Room Master evaluates the threshold values in ascending order,
i.e. first of all the threshold value for
OFF <-> Fan speed 1
is checked
followed by
Fan speed 1 <-> Fan speed 2
etc.
The correct method of function is only assured if the threshold value for
OFF <-> Fan speed 1
is less than the threshold value
Fan speed 1 <->
Fan speed 2
and this is less than
Fan speed 2 <-> Fan speed 3, etc.
Object value “Automatic ON/OFF”
switch on to the automatic
Options: 1
0
This parameter defines how to react to a telegram.
•
1:
Automatic is activated by a telegram with value 1.
•
0:
Automatic is activated by a telegram with value 0.