![ABB i-bus KNX Room Master Premium RM/S 2.1 Скачать руководство пользователя страница 102](http://html.mh-extra.com/html/abb/i-bus-knx-room-master-premium-rm-s-2-1/i-bus-knx-room-master-premium-rm-s-2-1_product-manual_3076102.webp)
ABB i-bus
®
KNX
Commissioning
© 2008 ABB STOTZ-KONTAKT GmbH
100
3.2.6.1.3 Parameter window
K: Shutter (6 A)
- Scene
In this parameter window all settings for the function
Scene
are undertaken.
This parameter window is visible if in parameter window
,
page 91, the parameter
Enable function scene
has been enabled.
How is a scene set?
Via the communication object Scene
•
The scene can be recalled.
•
The scene can be changed.
•
The scene can be saved.
An example:
Scene recall:
•
Send value 0-63 for the scene (no. 1-64) to the communication
object
Scene
.
Scene change and save:
•
Scene no. 24 is assigned to the output with the value move UP.
•
Scene no. 24 should be assigned to the output with the value
move DOWN:
- Set the output to move DOWN with a switch command.
- Send value 151 (128 + 23) for storage of scene number 24
to the communication object
Scene
.