![ABB i-bus KNX JRA/S 6.230.3.1 Скачать руководство пользователя страница 57](http://html.mh-extra.com/html/abb/i-bus-knx-jra-s-6-230-3-1/i-bus-knx-jra-s-6-230-3-1_product-manual_3075057.webp)
ABB i-bus
®
KNX
Commissioning
JRA/S 6.230.3.1 | 2CDC506083D0201 55
3.3.2.2.5
Output A,B: Switch actuator - Forced operation parameter window
All settings for the
Forced Operation
function are undertaken in this parameter window.
It is visible if the
Enable function Forced operation
parameter is enabled in Output A,B: Switch actuator
A Forced operation group object is available for every output.
The forced operation (a 1 bit or 2 bit communication object per output) sets the output in a defined state,
where – as long as the forced operation is active – it can only be changed via the communication object
forced operation.
The switch state after the end of forced operation can be set using the parameter
Contact pos. if forced
operation
.
•
Yes
: The following parameters appear:
Type of object "Forced operation"
Options:
1-bit
2 bit
Using the 2-bit group object, the output state is defined directly via the group object value. Control
of the output via the
Switch
group object is disabled as long as the output is forcibly switched ON or
OFF.
Содержание i-bus KNX JRA/S 6.230.3.1
Страница 1: ...ABB i bus KNX JRA S 6 230 3 1 Blind Roller Shutter Actuator with Binary Inputs Product Manual ...
Страница 2: ......
Страница 8: ...ABB i bus KNX General 6 2CDC506083D0201 JRA S 6 230 3 1 ...
Страница 14: ...ABB i bus KNX Device technology 12 2CDC506083D0201 JRA S 6 230 3 1 2 3 Dimension drawing 2CDC072028F0016 ...
Страница 142: ......
Страница 148: ...ABB i bus KNX Appendix 146 2CDC506083D0201 JRA S 6 230 3 1 Notes ...
Страница 149: ...ABB i bus KNX Appendix JRA S 6 230 3 1 2CDC506083D0201 147 Notes ...
Страница 150: ...ABB i bus KNX Appendix 148 2CDC506083D0201 JRA S 6 230 3 1 Notes ...
Страница 151: ......