ABB i-bus
®
KNX
Device technology
IPS/S 3.5.1 | 9AKK107680A8655 EN Rev. A 11
2
Device technology
IPS/S 3.5.1
The ABB i-bus
®
IP Interface Secure IPS/S 3.5.1 connects the KNX bus to an Ethernet network.
KNX telegrams can be sent to or received from other devices via the network.
The Interface can be used as a programming interface (ETS), and clients, e.g. Visualisations, can access
the KNX bus via the IPS/S 3.5.1.
The device uses the KNXnet/IP protocol and the KNXnet/IP Security protocol from the KNX Association
(tunneling) for communication.
The device is powered by 12 to 30 V DC or PoE (Power over Ethernet) to IEEE 802.3af class 1.
If both options are connected simultaneously, PoE will be used.
2.1
Technical data
Supply
Supply voltage U
s
12…30 V DC (+10% / -15%)
or PoE (IEEE 802.3af class 1)
Power loss
Maximum 1.8 W
Current consumption, supply voltage
Maximum 120 mA at 12 V
Rated voltage U
n
12 V DC
KNX current consumption
< 10 mA
Connections
KNX
Bus connection terminal
Operating voltage
Plug-in terminal
LAN
RJ45 socket for 10/100BaseT,
IEEE 802.3 networks, AutoSensing
Operating and display elements
Red LED and button
Assignment of the physical address
Green “On” LED
Ready indicator
Yellow “LAN/Link” LED
Network connection indicator
Yellow “Telegram” LED
KNX telegram traffic indicator
Degree of protection
IP 20
To EN 60 529
Protection class
II
To EN 61 140
Isolation category
Overvoltage category
III to EN 60 664-1
Pollution degree
2 to EN 60 664-1
2C
D
C
071
00
8F
001
7