Planning and application
94 2CDC508116D0203 | FCL/S x.6.1.1
4.4.5
Tabular overview of bus voltage recovery, download and ETS reset
Device general
Behavior
On bus voltage recovery
Download
After ETS reset, full down-
load and application up-
date
Transmission and
switching delay
Yes (can be parameterized)
None
None
Communication object
"In operation"
Sends after send delay.
Cycle time commences after
initialization.
Cycle time commences after
initialization.
Cycle time commences after
initialization.
Output: fan
Behavior
On bus voltage recovery
After download
After ETS reset, full down-
load and application up-
date
Status byte
Error bit is reset and set
again if necessary
Error bit is reset and set
again if necessary
Error bit is reset and set
again if necessary
Status messages
Sent if send reaction is set to
"Only after changing" or
"After a change or request".
Sent if send reaction is set to
"Only after changing" or
"After a change or request".
Sent if send reaction is set to
"Only after changing" or
"After a change or request".
Output control
Can be parameterized sepa-
rately for bus voltage failure
and recovery
Unchanged
Off
Start-up behavior
Unchanged
Unchanged
Canceled
Enable/disable commu-
nication object "Run-on"
Unchanged
Unchanged
Enabled
Run-on behavior
Stopping time restarts at
current speed.
Stopping time restarts at
current speed.
Canceled
Forced operation
Unchanged
Unchanged
Canceled
Automatic ON/OFF
Unchanged
Unchanged
On
Control value monitoring
in automatic mode
Monitoring time is restarted.
Control value fault is reset.
Monitoring time is restarted.
Control value fault is reset.
Monitoring time is restarted.
Control value fault is reset.
Limitations
Unchanged
Unchanged
Inactive
Output: Switch actuator
Reaction
On bus voltage recovery
After download
After ETS reset, full down-
load and application up-
date
Status messages
Sent if send reaction is set to
"Only after changing" or
"after a change or request".
Sent if send reaction is set to
"Only after changing" or
"After a change or request".
Sent if send reaction is set to
"Only after changing" or
"After a change or request".
Output control
Can be parameterized sepa-
rately for bus voltage failure
and recovery
Unchanged
Off
Staircase lighting time
Continues
Continues
Not active
Disable function Time
Unchanged
Can be parameterized
Not active
Permanent On
Unchanged
Unchanged
Not active