ABB i-bus
®
KNX
Commissioning
AA/S 4.1.2, AA/A 2.1.2 | 2CDC505163D0201 45
3.2.6
Parameter window A: Forced operation
This parameter window is shown if the corresponding function was enabled in
The function
Forced operation
allows you to adopt a specific output value that overrides the input value, by
sending a 1- or 2-bit command that applies predefined parameters. This output value can also be exited
again only after withdrawal of the forced operation command.
The difference between 1- and 2 bit-forced operations is that the latter allows you to assign two different
values: one for the forced Off status, e.g. 0 V, and another for the forced On status, e.g. 10 V.
Forced operation 1 takes priority over forced operation 2. But both must be canceled in order to continue in
normal mode.
Note
Forced operation is not affected by the characteristic. It is output directly.
Attention! Observe output range
< --- Note
Note
(see p. 26) must be observed.