ABB i-bus
®
KNX
Parameters
FCC/S 1.X.X.1 | 2CDC 508 200 D0211 Rev A 317
7.13.1.5.6.2
—
Dependent Parameter
On object value
Options:
0
1
0 or 1
•
1
: Sends the group object value 1 cyclically.
•
0
: Sends the group object value 0 cyclically.
•
0 or 1
: Sends the group object values 0 or 1 cyclically.
7.13.1.5.7
—
Dependent Parameter
Scan input after download, ETS reset and bus voltage recovery
Options:
No
Yes
•
No
: The object value is not scanned after a download, ETS reset or bus voltage recovery.
•
Yes
: The object value is scanned after a download, ETS reset or bus voltage recovery.
Note
Scanning starts once the device is ready for normal operation again after the download, ETS re-
set or bus voltage recovery. This can take up to 2 seconds.
7.13.1.6
Connect analog room control unit
In the
Setpoint adjustment
parameter window, you can set the
Connect analog room control unit to
physical device input a
parameter to allow an analog room control unit to be connected to the in-
put. You will not be able to change this in the
Input a
window unless you deactivate your selection
in the
Setpoint adjustment
window first.
This setting displays the dependent parameters
Send Status value
and
Send input status
cyclically
.
7.13.1.6.1
—
Dependent Parameter
Send status value
Options:
After a change
On change and cyclically
•
After a change
: Sends the value only after a change.
•
On change and cyclically
: Sends the value after a change, and cyclically. Enables the depen-
dent parameter
Send input status cyclically
.