ABB i-bus
®
EIB / KNX
Application and planning
This function can be used for example after a presentation to restore the
lighting to the state it was in beforehand.
3.2.4
8-bit scene
Short push
button action
Actuator
1 Actuator
2 Actuator
3
OFF
ON OFF
Retrieve scene no. <xx>
Fig. 4: Retrieve scene, 8-bit scene
In the 8-bit scene, the push button gives the actuator the instruction to
retrieve a scene. The scene is not stored in the push button but in the
actuator. All the actuators are addressed via the same group address. A
single telegram is sufficient to retrieve the scene.
A scene number is sent in the telegram value which must match the scene
number in the parameters of the actuator.
After a long push button action (for example), the actuators receive a save
command which causes them to store the current value issued by the
actuator as a new scene value.
Up to 64 different scenes are managed via a single group address. An 8-bit
scene telegram contains the following information:
- Number of the scene (1...64)
- Retrieve scene / store scene
3.2.5 Threshold
function
The threshold function monitors a 1-byte or 2-byte value. As soon as this
value exceeds or falls below a threshold value, the output can be switched.
The threshold values can be interpreted as hysteresis values:
Threshold values are hysteresis values
Output
Object “Threshold
value”
ON
OFF
Upper threshold
Lower threshold
ON
OFF
When the value exceeds the upper threshold or falls below the lower
threshold, the output is switched.