Operating manual HVL 120-0.3 

 

4  TECHNICAL DATA / DESIGN 

 

Technical data in accordance with EN 50123-5: 1997

 

 

Area of application: 

For DC current railway networks 
for indoor and outdoor 
applications 

Rated voltage U

r

50 V (DC) 

Highest withstand voltage U

w

60 V (DC) 

Limiting voltage U

s

120 V (DC) 

High-current strength: 

20 kA for 0.1 s 

1)

 

Current according to the resetting capability test I

rev

300 A for 60 s 

2)

 

Long-time current strength I

w

 without guarantee of resetting 

capability: 

500 A for 1800 s 

1)

 

LVL classification: 

LVLa 

Temperature range: 

-20°C to +45°C 

Height without accessories: 

123 mm 

Diameter without accessories: 

130 mm 

Weight without accessories: 

3.8 kg 

 

1)

 After responding, the resetting capability cannot be guaranteed. The protective function has been verified 

up to the specified values. The low voltage limiter then represents a low-impedance connection (short 
circuit). 
 

2)

 Up to this current value in the stated time period, the low voltage limiter resets itself back to its starting 

condition after responding. If the current is higher than this or if the time period is greater than that stated, 
the resetting capability cannot be guaranteed. If the low voltage limiter does not reset to its starting condition, 
it becomes permanently conductive. In this way, the protective function continues to be fulfilled up to 
parameters as stated at 

1).

 

 
 

Technical data for the integrated metal oxide varistor in accordance with IEC 60099-4: 2001

 

 

Nominal discharge current I

n

20 kA 8/20 µs 

High-current impulse I

hc

100 kA 4/10 µs 

Residual voltage at nominal discharge current U

p

: 380 

 
 

Type plate 

 

 

 

 

 

 

Name of manufacturer 

 

abb

 

 

 

 

1HC0023892 AA 

EN 

Page 4 / 12

 

 

 

 

 

 

 

HVL 

Type designation (HVL = Hybrid Voltage Limiter) 

 

 

 

Low Voltage Limiter

    U

s

 Limiting 

voltage 

 

 

 

HVL 120-0.3

 

 

I

rev

 

Current according to the resetting capability test 

 

 

 

 

 

 

 

 

acc. EN 50123-5 

 

I

w

 

Long-time current strength without guarantee 

 

 

 

 

 

 

 

of resetting capability 

 

U

s

 120 

V  I

n

 

20 kA 8/20 µs 

 

 

 

 

I

rev

 300 

A  U

p

380 V 

 

I

n

 

Nominal discharge current 

 

I

w

 500 

A     

  

 

Содержание HVL 120-0.3

Страница 1: ...L DATA DESIGN 4 5 OPERATION AND STRUCTURE 6 6 ASSEMBLY AND INSTALLATION 7 7 MAINTENANCE SERVICING 9 8 SQS CERTIFICATE 11 9 EU DECLARATION OF CONFORMITY 11 Published by Contact details ABB Switzerland Ltd Phone 41 58 585 29 11 Surge arresters Telefax 41 58 585 55 70 Jurastrasse 45 E mail sales sa ch abb com CH 5430 Wettingen 1 www abb com arrestersonline Switzerland Subject to change without notice...

Страница 2: ...of installation ABB accepts no liability for direct or indirect damage arising from the use or misuse of this product 2 DESCRIPTION AND FUNCTION Stationary installations for the supply of railway traction current employ the rails amongst other means as the return path for the traction current In the case of DC current railways electrically conductive parts or structures located in the area of the ...

Страница 3: ...miter Each consignment is accompanied by final inspection record Scope of supply Low voltage limiter Fixing bracket for the low voltage limiter T bracket for cable connection Bolts and tension washers Final inspection record 1 x 1 x 1 x 4 x 1 x Following delivery each consignment must be checked for completeness and correctness compare against the order and delivery documents In the case of incomp...

Страница 4: ...s current value in the stated time period the low voltage limiter resets itself back to its starting condition after responding If the current is higher than this or if the time period is greater than that stated the resetting capability cannot be guaranteed If the low voltage limiter does not reset to its starting condition it becomes permanently conductive In this way the protective function con...

Страница 5: ...l HVL 120 0 3 Up Residual voltage at nominal discharge current In No HA Serial number Dimensions Low voltage limiter T bracket for cable connection Fixing bracket for the low voltage limiter 1HC0023892 AA EN Page 5 12 ...

Страница 6: ... voltage U applied to the low voltage limiter and typically lies in the region of several hundred microseconds The duration of the overvoltage is therefore the controlling factor for the value of the voltage limitation If the duration lies in the region of several hundred microseconds then the characteristic curve of the metal oxide varistor alone defines the voltage limitation for example 380 V a...

Страница 7: ...r must only be assembled installed and operated with the supplied accessories for its intended purpose and in accordance with its specifications o Modifications and repairs to the low voltage limiter itself and to its mounting parts are prohibited o If special problems arise which were not covered or were insufficiently covered in this operating manual please contact ABB Schweiz Before beginning a...

Страница 8: ...ure For this purpose use a secure working platform and wear your personal protective equipment The contact surface to which the low voltage limiter is to be fitted by means of the fixing bracket must be flat and clean The mounting position of the low voltage limiter can be freely chosen It must be noted however that the type plate and serial number should remain easily readable without removing th...

Страница 9: ...ltage limiter should be cleaned For this we recommend that a soft cloth is used with warm water and a mild household cleaner do not use solvents or abrasive cleaning agents Faults and reserve equipment The low voltage limiter is a protective equipment element and therefore overloading can never be completely excluded Depending on the number of units in operation it is recommended that a suitable n...

Страница 10: ...under Point 1 and Point 2 must be repeated 4 The HVL 120 0 3 must be shorted out with a conductor of sufficient dimensions observe the national regulations and the requirements of the railway network operator This conductor must be arranged to ensure that detachment of the connection during removal of the HVL 120 0 3 cannot occur 5 Take a further measurement of the voltage via the connections of t...

Страница 11: ...red and brought into service in conformity with the EC directive 73 23 EEC Company ABB Switzerland Ltd Surge arresters Jurastrasse 45 CH 5430 Wettingen Switzerland The following EC directives and harmonised standards have been applied EC directive 73 23 EEC low voltage electrical equipment The following European standards have been applied Railway applications stationary installations DC current s...

Страница 12: ...Operating manual HVL 120 0 3 1HC0023892 AA EN Page 12 12 ...

Отзывы: