![ABB HVC Скачать руководство пользователя страница 74](http://html.mh-extra.com/html/abb/hvc/hvc_installation-manual_1093074.webp)
HVC 450 kW E-Bus Charger Installation Guide
Revision: 1.2
COMPANY CONFIDENTIAL
Date released: 16-08-2018
Page
74
of
128
A
Terminal block
B
AC utility power cable
1. Move the cable towards the terminal block (A).
2. Strip 0.43 Inch of the insulation from the ends of the wires.
3. Crimp a ferrule onto the end of the wire.
4. Loosen the connector screws.
5. Insert the wires into the connectors, see table below:
Functional description
Connector
Wire color
GND
X341-1
Green/yellow
L1
X341-2
Black
L2
X341-3
Red
L3
X341-4
Blue
6. Tighten the connector screws.
5.8.3. Connect the Interlock cable
Interlock cable connection in the
slave 2
HVC 150S
:
A
Terminal block
B
Interlock cable from/to slave 1 HVC 150S
1. Move the cable towards the terminal block (A).
2. Strip 0.43 Inch of the insulation from the ends of the wires.
3. Crimp a ferrule onto the end of the wire.
4. Loosen the connector screws.
5. Insert the wires into the connectors, see table below:
Functional description
Connector
Wire number
Interlock In (slave 1 HVC 150S)
X286-4
2
Interlock Out (slave 1 HVC 150S)
X286-8
1
Interlock GND
X286-9
Shield
See also Appendix H
Signal connection diagram
.
6. Tighten the connector screws.