![ABB HVC-C 100-150 kW Скачать руководство пользователя страница 100](http://html.mh-extra.com/html/abb/hvc-c-100-150-kw/hvc-c-100-150-kw_installation-manual_2837984100.webp)
20.12.6
PE cables
Parameter
Specification
Type
Unshielded
Number of cores
4
Core identification
green-yellow
Diameter
10 - 14mm
Cross section
35 mm²
Conductor
Fine strand copper wire according to VDE 0295 Cl.
5/ IEC 60228 Cl. 5
Insulation
PVC that is serviceable for outdoor use, UV-pro-
tected, and oil resistant
Nominal voltage Uo/U
450/750 Vac
Minimum test voltage
4 kV
Ambient temperature range
-40 ºC to 80 ºC
Strip length
Acc. to the used wire end ring
20.12.7
Interlock cables
Parameter
Specification
Type
Shielded (tinned copper braid)
Number of pairs
1 x 2
Core identification
Acc. to DIN 47100
Cross section
0.75-2.5 mm²
Diameter
5 - 10mm
Conductor
Fine strand copper wire
Insulation
PVC that is serviceable for outdoor use, UV-
protected, and oil resistant
Characteristic impedance
120 Ω ± 10%
Test voltage
1.5 kV
Ambient temperature range
-40ºC to 80ºC
Strip length
11 mm
20.12.8
Ethernet cables
Parameter
Specification
Type
Shielded (tinned copper braid)
Number of (twisted) pairs
4 x 2
Core identification
Acc. to DIN 47100
Cross section
0.5 - 0.75 mm²
Diameter
5 - 10mm
Conductor
Fine strand copper wire
Insulation
PVC that is serviceable for outdoor use, UV-
protected, and oil resistant
Technical data
100
6AGA000007-0611-EN | 001
Содержание HVC-C 100-150 kW
Страница 1: ...Installation manual HVC C 100 150 kW Overnight Copyright ABB All rights reserved CCS and CR variant ...
Страница 42: ...P a g e l e f t i n t e n t i o n a l l y b l a n k 42 6AGA000007 0611 EN 001 ...
Страница 79: ...P a g e l e f t i n t e n t i o n a l l y b l a n k 6AGA000007 0611 EN 001 79 ...
Страница 106: ......