A
Charge post
X1
Total required width for the charge
post
X2 Space required for the air inlet and
to open the side panel
X3 Space required at the sides to open
the door
X4 Total required width to open the
door
X5 Required width to open the side
panel
Y1
Space required for cable
replacement
Y2 Total required depth for the charge
post
Y3 Maximum sideway reach of the
wheelchair user
Y4 Space required to open the door
Y5 Required depth to open the side
panel
Parameter
Specification
[mm]
[in]
X1
1490
58.7
X2
450
17.7
X3
105
4.1
X4
800
31.5
X5
345
13.6
Y1
400
15.7
Y2
775
30.6
Y3
254
10
Y4
490
19.3
Y5
345
13.6
12.16.3
Charge post: exceptions for bollards and other minor fixed
obstacles
Note:
The bollards or minor fixed obstacles must have a maximum diameter of
150 mm (6 in), to permit service or maintenance operations.
Technical data
84
9AKK107992A6488-EN | 004
Содержание HP CP500
Страница 103: ...Technical data 9AKK107992A6488 EN 004 103 ...
Страница 104: ......