6
-
LOAD
2
-
LOAD
8
-
LOAD
Figure 23 2
-
Load to 6 or 8
-
Load Conversion
Connect Input Feeds
Lug landings are 3/8
-
16 on
1”
centers. See Figure 3 and Figure 4.
1.Input Feeds
-
Run and terminate input feed cables to the Load Shunt Bus of each load bus.
2.
Input Feed Returns
-
Run and terminate input feed return cables to the Load Return Bus.
•
Internal Return Bus
-
Figure 3 and Figure 4
•
External Return Bus
-
Figure 10 and Figure 11
3.Torque hardware to 240 in
-
lb with
9/16”
socket.
Connect Breaker/Fuse Loads
Lug Landings:
•
Distribution Connections
-
1/4
-
20 on
5/8”
centers.
•
Adapter Bus Kits –
3/8
-
16
on
1”
centers.
See Figure 6, Figure 7, and Figure 9.
1.
Two
-
Pole and Three
-
Pole Adapter Bus Kits
-
Install Two
-
Pole and Three
-
Pole Adapter Bus Kits
for each Breaker/Fuse Load fed by a Two
-
Pole and Three
-
Pole protector
-
.
•
Secure the Mount Adapter Bus Kits to the associated connection landings with 1/4
-
20
hardware.
•
Torque to 65 in
-
lb with
7/16”
socket.
Содержание H569-445
Страница 6: ...Page 6 Copyright 2021 ABB All rights reserved ...
Страница 13: ...Page 13 Copyright 2021 ABB All rights reserved Figure 6 Distribution Connections G7 and G8 ...
Страница 22: ...Page 22 Copyright 2021 ABB All rights reserved ...
Страница 27: ...Page 27 Copyright 2021 ABB All rights reserved Figure 21 Top Feed to Bottom Feed Cabinet Conversion G7 and G8 ...
Страница 32: ...Page 32 Copyright 2021 ABB All rights reserved Figure 25 Customer Interface Board ...
Страница 34: ...Page 34 Copyright 2021 ABB All rights reserved ...
Страница 39: ...Page 39 Copyright 2021 ABB All rights reserved Wiring Schematics Figure 27 Panel Wiring Schematic G7 and G8 ...
Страница 40: ...Page 40 Copyright 2021 ABB All rights reserved Figure 28 Panel Wiring Schematic G101 and G102 ...
Страница 44: ...Page 44 Copyright 2021 ABB All rights reserved ...