14
Installation and maintenance guide
1ZSC000563-AAB EN, REV. 6, 2019-09-12
Load on the bushing flange
G006509
1
Bending moment
2
Compressive or tensile load
3
Shearing load
4
Bushing flange
Type
Maximum bending moment on the
bushing flange:
Maximum load on the bushing flange in
service:
Test load (kNm)
In operation (kNm) Shearing load (kN) Compressive or
tensile load (kN)
GSBK 170
20
10
10
50
GSBK 245
40
20
14
70
GSBK 362
80
40
20
10
GSBK 420
80
40
20
10
GSBK 550
80
40
20
10
GIS pressure
The limit SF
6
gas pressures for the GIS side of the bushing.
Type
Type test pressure 1
minute MPa
abs
Routine test pressure 1
minute MPa
abs
Maximum service
pressure MPa
abs
GSBK 170
2.55
1.25
0.85
GSBK 245
2.55
1.25
0.85
GSBK 362
2.55
1.25
0.85
GSBK 420
2.55
1.25
0.85
GSBK 550
2.55
1.25
0.85
Содержание GSBK 170
Страница 1: ...1ZSC000563 AAB EN REV 6 2019 09 12 Transformer bushing type GSBK Installation and maintenance guide ...
Страница 46: ...46 Installation and maintenance guide 1ZSC000563 AAB EN REV 6 2019 09 12 ...
Страница 52: ...52 Installation and maintenance guide 1ZSC000563 AAB EN REV 6 2019 09 12 ...
Страница 54: ...54 Installation and maintenance guide 1ZSC000563 AAB EN REV 6 2019 09 12 ...
Страница 62: ...62 Installation and maintenance guide 1ZSC000563 AAB EN REV 6 2019 09 12 ...
Страница 66: ...66 Installation and maintenance guide 1ZSC000563 AAB EN REV 6 2019 09 12 ...
Страница 70: ......
Страница 71: ......