JSON Communication
G13
141
2CMC489001M0201
User Manual
Revision: A
6.3.48 POST /meters/<serial>/transformersettings
A POST call to /meters/<serial>/transformersettings updates transformer settings
of meter.
Protected
Yes (Authentication required)
Request
POST /meters/ABB_3/transformersettings HTTP/1.1
Host: 192.168.1.12
Content-Length: 54
Authorization: Basic XXXXXXXXXXXXXXX=
{"ctnum":"1","ctdenum":"1","vtnum":"1","vtde-
num":"1"}
Description
• ctnum [Int] - CT numerator
• ctdenum [Int] - CT de-nominator
• vtnum [Int] - VT numerator
• vtdenum [Int] - VT de-nominator
Examples
• https://192.168.1.12/meters/ABB_8/transformersettings
Response
• 200 OK
HTTP/1.1 200 OK
Content-Type: application/json
Server: embOS/IP
Transfer-Encoding: chunked
Link:/lasterror/0
{"status":"success"}
• 500 Internal Server Error
HTTP/1.1 500 Internal Server Error
Server: embOS/IP
Accept-Ranges: bytes
Content-Length: 64
Content-Type: application/json
{
"status":"error",
"des":"received invalid response from COSEM."