2CMC489001M0201
166
G13
Revision: A
User Manual
JSON Communication
Response
•
200 OK
HTTP/1.1 200 OK
Content-Type: application/json
Server: embOS/IP
Transfer-Encoding: chunked
Link:/lasterror/0
{
"status":"success"
}
• 500 Internal Server Error
HTTP/1.1 500 Internal Server Error
Server: embOS/IP
Accept-Ranges: bytes
Content-Length: 64
Content-Type: application/json
{
"status":"error",
"des":"received invalid response from COSEM."
}
6.3.58 GET /meters/<serial>/energy/resetcounter
A GET call to /meters/<serial>/energy/resetcounter returns reset count of resetta-
ble energy values of requested meter.
Reset counter is incremented each time these registers are reset. It holds number
of times the resettable registers are reset.
Protected
Yes (Authentication required)
Request
GET /meters/<serial>/energy/resetcounter HTTP/1.1
Authorization: Basic XXXXXXXXXXXXXXX=
Examples
• https://192.168.1.12/meters/ABB_8/energy/resetcounter
Содержание G13
Страница 1: ...G13 User Manual ...
Страница 2: ......
Страница 3: ...G13 User Manual Document ID 2CMC489001M0201 Revision A 2013 04 25 ...
Страница 8: ...Table of Content G13 4 2CMC484002M0201 User Manual Revision A ...
Страница 50: ...2CMC489001M0201 46 G13 Revision A User Manual Meter Settings 4 Set Frequency 5 Select Energy Type 6 Click Send ...
Страница 249: ...JSON Communication G13 245 2CMC489001M0201 User Manual Revision A ...