Mounting
30
FV4000 / FS4000
D184B097U02
4.10 Transmitter orientation
During installation, the transmitter hosing can be turned to a position appropriate for reading
requirements. A simple mechanical stop in the transmitter housing prevents rotation in excess
of 330°. This stop protects the cable running from the flowmeter sensor.
G00705
1
2
Fig. 21: Rotating the transmitter housing
1
Bolt
2
Stop screw
1.
Unscrew the stop screw on the transmitter housing with a 4 mm Allen key.
2.
Push the bolts out.
3.
Turn the transmitter housing in the required direction.
Warning - Potential damage to parts
The transmitter housing must not be lifted up, since this could tear away the cable coming out
of the housing.
4.
Put the bolts back in.
5.
Fasten the stop screw.