What to do
AUX code(s)
Description
Warning
Code
0000 000A
Check PLC program
status.
PLC gave config
where fpar_crc does
not match to calcu-
lated one
If warning persists,
gather the AUX codes
from this fault and con-
tact ABB.
If warning persists,
gather the AUX codes
from this fault and con-
tact ABB.
0000 0010
Received new f-
parameters
Check PLC program
status.
0000 0011
Profisafe stack
stopped due to
profinet state
If warning persists,
gather the AUX codes
from this fault and con-
tact ABB.
Check PLC program
status.
0000 0012
Crc failure in cyclic
communication
If warning persists,
gather the AUX codes
from this fault and con-
tact ABB.
Calculate a new watch-
dog time. See section
PROFIsafe response
time.
0000 0013
Watchdog timeout in
cyclic communica-
tion
If the warning reoccurs,
gather the AUX codes
from this fault and con-
tact ABB.
0000 0014
PLC set bit4 (activ-
ate_fv) in cyclic
communication
Event messages
Description
Event
Code
FSX undefined event.
FSx undefined event
0xB795
If AUX = 0000 0000, no errors exist.
FSx diagnostics
0xB796
In any other case, gather the AUX codes from this event and contact
ABB.
LEDs
The adapter module is equipped with three bicolor diagnostic LEDs. The LEDs are described
below.
Fault tracing 183
Содержание FSPS-21
Страница 1: ... OPTIONS FOR ABB DRIVES FSPS 21 safety functions fieldbus module User s manual ...
Страница 2: ......
Страница 4: ......
Страница 11: ...Further information Table of contents 11 ...
Страница 12: ...12 ...
Страница 26: ...26 ...
Страница 38: ...38 ...
Страница 42: ...42 ...
Страница 46: ...46 ...
Страница 69: ...Configuring safety PLC 1 Select safety telegram to use on slot 2 Leave slot 1 empty PROFINET IO Start up 69 ...
Страница 72: ...Switch or router ABB drive ABB drive ABB drive PLC Safety PLC 72 PROFINET IO Start up ...
Страница 86: ...86 ...
Страница 136: ... Configuring FSPS 21 with TIA14 1 Open TIA and create a new project 2 Select your CPU from the list 136 PROFIsafe ...
Страница 144: ...19 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 20 Insert values to blocks 144 PROFIsafe ...
Страница 147: ...26 In device configuration right click FSPS icon and select Assign device name PROFIsafe 147 ...
Страница 155: ...Select Addresses tab to see the correct IO addresses PROFIsafe 155 ...
Страница 169: ...6 To check the Device number of the FSPS 21 module select the General tab PROFIsafe 169 ...
Страница 178: ... starting the system does not cause any danger 178 Start up ...
Страница 186: ...186 ...
Страница 192: ...192 ...
Страница 200: ...200 ...
Страница 208: ...208 ...
Страница 212: ......