94 PROFINET IO – Communication protocol
Example 5: Determining the source of the process data read
from the drive
PROFIdrive parameter 916 (394h) can be used to define which
data is read cyclically from the drive as application-specific process
data. In the example below, the parameter is used to determine
which drive parameter the contents of PZD3 are taken from.
Subindex
(IND) defines which process data word the required data
is transmitted in.
•
DP-V1 Write request:
DP
header
01 01 B0 2F 0A 0B 01 01 01 10 01 03 94 00 03
DP trailer
DP-V1 Response
PROFIdrive V3 Parameter Channel
Slot number
Subslot number
Index
Data length
Request reference
Request ID (01h = Read)
Number of parameters
Drive object ID
Number of elements
Attribute (10h = Value)
Parameter index
Subindex
DP-V1_Write_request_3.pdf
•
DP-V1 Read response:
PROFINET IO – Communication protocol 95
•
DP-V1 Read response:
Value
indicates the source of PZD3 as drive parameter 12.05
(0C.05h).
Diagnostic and alarm mechanism
The FENA adapter module has mechanisms for sending alarms
and saving diagnostics data to a fault buffer. An alarm is triggered
if the host or drive has faults in communication or operation. The
alarm and fault buffer mechanisms are enabled by default and can
be disabled with a configuration parameter (
21
Alarm disable
on
page
13
).
DP
header
01
01
B0
2F
08
0B
01
01
01
42
01
0C
05
DP
trailer
DP-V1 Response
PROFIdrive V3 Parameter Channel
Subslot number
Index
Data length
Request reference (mirrored)
Response ID
Drive object ID (mirrored)
Number of parameters
Format (42h = Word)
Number of values
Value of error
values
Slot number
DP-V1_Read_response_3.pdf
Value
indicates the source of PZD3 as drive parameter 12.05 (0C.05h).
Diagnostic and alarm mechanism
The FSPS-21 module has mechanisms for sending alarms and saving diagnostics data to
a fault buffer. An alarm is triggered if the host or drive has faults in communication or
operation. The alarm and fault buffer mechanisms are enabled by default and can be disabled
with a configuration parameter, see
FSPS-21 configuration parameters – group A (group
.
■
Alarm mechanism
When a fault situation occurs, the adapter module sends an alarm notification, which the
master station has to acknowledge. Alarm notifications can be acknowledged, viewed and
handled, for example, with Siemens S7 blocks OB82, OB83, OB86 and OB122.
PROFINET IO – Communication protocol 107
Содержание FSPS-21
Страница 1: ... OPTIONS FOR ABB DRIVES FSPS 21 safety functions fieldbus module User s manual ...
Страница 2: ......
Страница 4: ......
Страница 11: ...Further information Table of contents 11 ...
Страница 12: ...12 ...
Страница 26: ...26 ...
Страница 38: ...38 ...
Страница 42: ...42 ...
Страница 46: ...46 ...
Страница 69: ...Configuring safety PLC 1 Select safety telegram to use on slot 2 Leave slot 1 empty PROFINET IO Start up 69 ...
Страница 72: ...Switch or router ABB drive ABB drive ABB drive PLC Safety PLC 72 PROFINET IO Start up ...
Страница 86: ...86 ...
Страница 136: ... Configuring FSPS 21 with TIA14 1 Open TIA and create a new project 2 Select your CPU from the list 136 PROFIsafe ...
Страница 144: ...19 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 20 Insert values to blocks 144 PROFIsafe ...
Страница 147: ...26 In device configuration right click FSPS icon and select Assign device name PROFIsafe 147 ...
Страница 155: ...Select Addresses tab to see the correct IO addresses PROFIsafe 155 ...
Страница 169: ...6 To check the Device number of the FSPS 21 module select the General tab PROFIsafe 169 ...
Страница 178: ... starting the system does not cause any danger 178 Start up ...
Страница 186: ...186 ...
Страница 192: ...192 ...
Страница 200: ...200 ...
Страница 208: ...208 ...
Страница 212: ......