![ABB FSO-21 Скачать руководство пользователя страница 44](http://html.mh-extra.com/html/abb/fso-21/fso-21_user-manual_2728044.webp)
44 Overview
Safe position
With the FSO-21 module, FSE-31 module, safety encoder and PROFINET adapter
(FENA-21 or FPNO-21 module), it is possible to utilize safe position data via a safety
PLC. To use the safe position data, a PROFIsafe connection and the PS2-profile are
needed. See section
on page
.
Note:
With an HTL encoder, the position data can be lost with power loss, if there is a
failure in any of the devices in the safety chain, or the bit Speed_Pos_value_valid of
the PROFIsafe profile indicates invalidity. Rezeroing is needed to verify the position.
Motor speed feedback
FSO module needs motor speed feedback to perform safety functions. It can be
either a measured speed from a safety encoder or a safe speed estimate. With
FSO-12 module only safe speed estimate is available. FSO-21 module supports both
safe speed estimate and measured speed from an HTL safety encoder via the
FSE-31 encoder interface module. Depending of the motor speed feedback, safety
functions operate slightly differently (for example, when the indications turn on and
off) due to inaccuracy in safe speed estimate. The feedback type has also an effect
on how the safety functions are configured. See chapter
for more
information on the difference between the measured speed feedback (encoder) and
safe speed estimate.
Note:
With safe speed estimate, the FSO module and the drive motor control have an
independent motor model of their own. The accuracy of these two speed estimates
can differ from each other, especially in the low speed region.
Safe speed estimate
Note:
Safe speed estimate cannot be used with a DCS880 drive.
With safe speed estimate, the FSO module uses the drive electrical output frequency
measurement to estimate the motor speed. To have the most accurate motor model
for the safe speed estimation, it is necessary to set the motor nominal values to
parameters
The FSO module has two safe speed estimation data channels. Speed in channel
one is received from the drive (
), and speed in channel two is
calculated by FSO module (
). FSO compares these two speed
data sources. If the values differ too much, the FSO module detects it and goes into
the Fail-safe mode.
The nominal speed and nominal frequency of the motor must be set according to the
motor type designation label for the FSO module. See section
It must be considered in the risk assessment of the application whether the safe
speed estimate can be used.
Содержание FSO-21
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 21 safety functions module User s manual ...
Страница 4: ......
Страница 16: ...16 Safety instructions ...
Страница 34: ...34 Safety information and considerations ...
Страница 52: ...52 Overview ...
Страница 236: ...236 PROFIsafe ...
Страница 265: ...PROFIsafe 265 2 Select your CPU from the list 3 Install the FENA 21 GSDML file ...
Страница 275: ...PROFIsafe 275 20 In ABB_Drive FB add blocks DPRD_DAT and DPWR_DAT 21 Insert values to blocks ...
Страница 282: ...282 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 286: ...286 PROFIsafe ...
Страница 304: ...304 Installation ...
Страница 400: ...400 Configuration ...
Страница 488: ...488 Verification and validation ...
Страница 506: ...506 Fault tracing ...
Страница 514: ...514 Maintenance ...
Страница 536: ...536 Technical data ...
Страница 538: ...538 Dimension drawings 3AXD50000018513 ...