346 Verification and validation
Validation of the SMS functions
WARNING!
If the SMS validation is to be performed with the machinery
coupled to the motor, make sure that the machinery is able to withstand the
fast speed changes and the set maximum speed.
Validation of the SMS functions, version 1
1. Make sure that the SMS function is configured correctly according to your design.
For a configuration example, see section
How to configure SMS, version 1
page
. Check these settings:
Activation:
•
Functionality:
•
•
.
If possible, test the SMS trip limit in practice:
2. Make sure that you can ran and stop the motor freely.
3. Start the drive and accelerate to a speed higher than
4. Makes sure that the FSO module detects the over speed and activates the SSE
function.
5. Make sure that the SSE is configured according to the application safety
requirements.
6. Make sure that the acknowledgement of the SSE function is only possible when
the motor is in safe state.
Validation of the SMS function, version 2
1. Make sure that the SMS function is configured correctly according to your design.
For a configuration example, see section
How to configure SMS, version 2
page
. Check these settings:
Activation:
•
Functionality:
•
•
•
•
Содержание FSO-12
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 26: ...26 Introduction to the manual The PROFIsafe certificate for the FSO 12 module is attached below ...
Страница 36: ...36 Safety information and considerations ...
Страница 136: ...136 Safety functions ...
Страница 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 200: ...200 PROFIsafe ...
Страница 326: ...326 Start up ...
Страница 386: ...386 Dimension drawings ...