Configuration 257
Configuring SAR
How to configure SARn
To configure the SARn (n = 0…1), set the FSO parameters listed below to appropriate
values using the Drive composer pro PC tool. See parameter groups
page
on page
. See also section
on page
Example:
The figure below shows an example of a SAR0 monitoring set-up:
• SAR0
• ramp time from Scaling speed to zero: 1000 ms
200.102 SAR0 ramp time to zero
= 1000 ms
)
• Scaling speed: 1500 rpm (
1500 rpm
)
• initial range for monitoring: 100 ms (
100 ms
)
• minimum allowed ramp time: 500 ms
500 ms
)
• maximum allowed ramp time: 1000 ms
=
1500 ms
).
Note:
If you use SAR1 in several safety functions at the same time, tune it according
to the function which requires the tightest monitoring range.
= 500 ms
= 1500 ms
1000 ms
= 1500 rpm
SAR0
Time
Speed
= 100 ms
Содержание FSO-12
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 26: ...26 Introduction to the manual The PROFIsafe certificate for the FSO 12 module is attached below ...
Страница 36: ...36 Safety information and considerations ...
Страница 136: ...136 Safety functions ...
Страница 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 200: ...200 PROFIsafe ...
Страница 326: ...326 Start up ...
Страница 386: ...386 Dimension drawings ...