Configuration 225
Configuring the safety fieldbus communication
How to configure the safety communication with PROFIsafe
To configure the safety fieldbus communication between the FSO module and a
safety PLC, set the FSO parameters shown in the figure below to appropriate values
using the Drive composer pro PC tool. See parameter groups
on page
on page
and
.
In addition, you must install the PROFINET fieldbus adapter module to the drive and
set up the safety communication network between the modules as described in
chapter
Example
:
• PROFIsafe communication activated
Version 1
and
=
PROFIsafe
)
• Speed scaling: 1500 rpm
SBUSGEN. 06 Safety fieldbus speed scaling
=
1500 rpm
)
• the FSO module generates a fault message if the module is passivated due to
safety fieldbus problems
(
Fault
)
• the FENA module is connected to option slot 1
FBA A
and
1
)
• PROFIsafe profile ABB_PS1 in use
PROFIsafe. 12 PROFIsafe telegram type
=
0x221
)
• IP address of the FENA module: 1
PROFIsafe.11 PROFIsafe F_Dest_Add
= 1
)
=
PROFIsafe
= FBA A
=
1
=
0x221
= Version 1
= 1500 rpm
= 1
FENA
Safety PLC
FSO
ACS880 drive
= Fault
Содержание FSO-12
Страница 1: ... OPTIONS FOR ABB DRIVES FSO 12 safety functions module User s manual ...
Страница 4: ......
Страница 12: ...12 Table of contents ...
Страница 26: ...26 Introduction to the manual The PROFIsafe certificate for the FSO 12 module is attached below ...
Страница 36: ...36 Safety information and considerations ...
Страница 136: ...136 Safety functions ...
Страница 196: ...196 PROFIsafe 5 To read the diagnostic messages select the I O Device Diagnostics tab ...
Страница 200: ...200 PROFIsafe ...
Страница 326: ...326 Start up ...
Страница 386: ...386 Dimension drawings ...