Electrical
connections
D184B097U02
FV4000 / FS4000
33
5.1
Cable connection area
5.1.1 HART
design
The transformer has a two-wire design. This means that the supply voltage and the measuring
signal (4 ... 20 mA) are routed on the same wire. An additional switching output is also
available.
G00711
31
1
2
3
32
41
42
Fig. 23: Cable connection area
1
Current output terminals
2
Switching output terminals
3
Functional ground
Pin configuration
Connection
Description
31 Supply
power
32 Supply
power
41
Switching
42
Switching output -
Functional ground
Supply power (terminals 31 / 32)
Standard
14 ... 46 V DC
Hazardous area design
See chapter 11 "Ex relevant specifications".
Residual ripple
Maximum 5 % or. ± 1.5 Vpp
Power consumption
< 1 W
Содержание FS4000
Страница 1: ...Operating Instruction D184B097U02 Vortex Flowmeter Swirl Flowmeter FV4000 FS4000 ...
Страница 11: ...Safety D184B097U02 FV4000 FS4000 11 1 6 2 2 Name plates Fig 2 Name plate Fig 3 Name plate hazardous area ...
Страница 116: ...Appendix 116 FV4000 FS4000 D184B097U02 ...
Страница 117: ...Appendix D184B097U02 FV4000 FS4000 117 ...
Страница 118: ...Appendix 118 FV4000 FS4000 D184B097U02 ...
Страница 119: ...Appendix D184B097U02 FV4000 FS4000 119 ...
Страница 120: ...Appendix 120 FV4000 FS4000 D184B097U02 ...
Страница 125: ......