Grounding of the IP00-protected filter
WARNING!
The filter is grounded through the four fastening screws to its mounting plate.
Ensure that the mounting plate has a proper connection to the nearest
grounding (PE) busbar/terminal. If that is not the case, use a separate
grounding conductor between the filter frame and the PE busbar/terminal.
■
Connections to input terminals U1, V1, W1
The input terminals (U1, V1, W1) of the filter are made of aluminium. Use cable lugs
suitable for aluminium busbars and joint grease to avoid corrosion and to ensure good
electrical connection. The oxide layer must be scrubbed off from the joints before
applying the grease. ABB recommends to
•
use screws included in the delivery
•
retighten the connections 30 minutes after their installation.
■
Output terminals U2, V2, W2
The output terminals (U2, V2, W2) of the filter are tin-plated copper.
■
Strain relief of cables
Secure the cables mechanically.
Installation 25
10
Содержание FOCH
Страница 1: ...OPTIONS FOR ABB DRIVES FOCH filters Hardware manual...
Страница 2: ......
Страница 4: ......
Страница 12: ...12...
Страница 16: ...16...
Страница 22: ...FOCH0320 52 22 Installation...
Страница 24: ...Installation illustrations of an enclosed IP22 filter FOCH0320 52 FOCH0320 52 24 Installation...
Страница 26: ...26...
Страница 31: ...Dimension drawings The dimensions are given in millimetres and inches below 6 Dimension drawings 31...
Страница 32: ...FOCH0260 70 32 Dimension drawings...
Страница 33: ...FOCH0320 50 FOCH0610 70 and FOCH0875 70 Dimension drawings 33...
Страница 34: ...FOCH0260 72 34 Dimension drawings...
Страница 35: ...FOCH0320 52 Dimension drawings 35...
Страница 36: ...36...