Binary value object
Present value access
type
Default active/ Inact-
ive text
Description
Default object name
Object
ID
R
RUN / STOP
Run status of drive
RUN-STOP-Monitor
BV0
R
REVERSE / FORWARD
Rotational direction of
the motor
Direction-Monitor
BV1
R
FAULT / OK
Actual fault status of
drive
OK-FAULT-Monitor
BV2
R
EXT2 / EXT1
Actual control source
EXT1-EXT2-Monitor
BV3
R
HAND / AUTO
Actual operating
mode
HAND-AUTO-Monitor
BV4
R
WARNING / OK
Actual warning status
Warning-Monitor
BV5
R
READY / NOT- READY
Actual ready status
Ready-Monitor
BV7
R
YES / NO
Actual at setpoint
status
At-Setpoint-Monitor
BV8
R
ENABLE / DISABLE
Actual run enabled
status
Enabled-Monitor
BV9
C
RUN / STOP
Command to start
drive
RUN-STOP-Command
BV10
C
REVERSE / FORWARD
Command to rotation-
al direction
Direction-Command
BV11
C
ENABLE / DISABLE
Command to Run Per-
missive command
Run- Permissive-Com-
mand
BV12
C
EXT2 / EXT1
Command to External
1 or External 2
EXT1-EXT2-Command
BV13
W
RESET / NO
Command to fault re-
set
Fault-Reset-Command
BV14
R
LOCK / UNLOCK
Actual status of para-
meter lock.
Lock-Parameters
BV17
C
ON / OFF
Command the drive
into BACnet Control
Override. In this mode
BACnet acquires drive
control from its nor-
mal source.
Control- Override-
Command
BV18
Note: The HAND mode
of the panel has prior-
ity over BACnet Con-
trol Override.
Communication protocol 45
Содержание FBIP-21 BACnet/IP
Страница 1: ... OPTIONS FOR ABB DRIVES CONVERTERS AND INVERTERS FBIP 21 BACnet IP adapter module User s manual ...
Страница 2: ......
Страница 4: ......
Страница 8: ...8 ...
Страница 14: ...14 ...
Страница 38: ...38 ...
Страница 50: ...50 ...
Страница 58: ...58 ...
Страница 62: ...62 ...
Страница 71: ...Appendix D BACnet conformance certificate 23 Appendix D BACnet conformance certificate 71 ...
Страница 72: ...72 Appendix D BACnet conformance certificate ...