Start-up
Contents of this chapter
This chapter contains the start-up instructions for the extension adapter.
Defining node IDs for option modules
You must define a node ID for each option module connected to the FEA-03 F-series
extension adapter. The node ID is a two-digit decimal number that must be unique for each
option module connected to the drive. It is possible to set 96 different node IDs (04...99).
Values 00, 01, 02, and 03 are reserved. Define the node IDs using the mechanical switches
A and B (Slot 1) and/or C and D (Slot 2). Switches A and C define the first digit and switches
B and D the second digit of the node ID.
Setting the drive parameters
Set the node IDs in the drive control program according to the option module type.
For example, in ACS880 primary control program the parameters are:
• I/O extension modules: parameters
14.02 Module 1 location
,
15.02 Module 2 location
or
16.02. Module 3 location
• FEN encoder interface modules: parameters
91.12 Module 1 location
or
91.14 Module 2
location
.
See the applicable drive firmware manual for more information.
6
Start-up 23