EN – R6…R9 Quick installation guide 27
R0-
R4
R6-
R9
R6-
R9
EN
DA
DE
ES
FI
FR
IT
NL
PL
PT
RU
SV
TR
ZH
ZH
Check the insulation of the power cables and the motor
Check the insulation of the input cable according to local regulations before connecting
it to the drive.
See figure
on page
1. Check the insulation of the motor cable and motor before connecting it to the
drive. Measure the insulation resistance between each phase conductor and then
between each phase conductor and the Protective Earth conductor using a
measuring voltage of 1000 V DC. The insulation resistance of an ABB motor must
exceed 100 Mohm (reference value at 25 °C or 77 °F). For the insulation
resistance of other motors, see the manufacturer’s instructions.
Note:
Moisture inside the motor casing will reduce the insulation resistance. If
moisture is suspected, dry the motor and repeat the measurement.
Check the compatibility with IT (ungrounded) and corner-
grounded TN systems
EMC filter
The internal EMC filter is not suitable for use on an IT (ungrounded) system or on a
corner-grounded TN system. Disconnect the EMC filter before connecting the drive to
the supply network. Check the table on page
.
WARNING!
Do not install the drive with the internal EMC filter connected on an
IT system (an ungrounded power system or a high-resistance-grounded [over
30 ohms] power system), otherwise the system will be connected to ground potential
through the EMC filter capacitors of the drive. This can cause danger, or damage the
drive.
Do not install the drive with the internal EMC filter connected on a corner-grounded
TN system, otherwise the drive will be damaged.
Note:
When the internal EMC filter is disconnected, the drive EMC compatibility is
considerably reduced.
Ground-to-phase varistor
The ground-to-phase varistor is not suitable for use on an IT (ungrounded) system.
Disconnect the ground-to-phase varistor before connecting the drive to the supply
network. Check the table on page
Содержание EN Series
Страница 1: ...中文 13 English 41 ABB 标准变频器 快速安装和启动指导 ACS580 01 变频器 外形尺寸 R6 至 R9 R6 R9 ZH EN ...
Страница 16: ...16 ZH R6 R9 快速安装指南 R0 R4 R6 R9 R6 R9 ZH DA DE ES FI FR IT NL PL PT RU SV TR ZH ...
Страница 23: ...ZH 快速启动指南 23 R0 R4 ZH DA DE ES FI FR IT NL PL PT RU SV TR ZH 根据需要设置参数 选择一个参数并按 编辑 进行调节后 按 返回 返回初始设置 ...
Страница 24: ...24 ZH 快速启动指南 R0 R4 ZH DA DE ES FI FR IT NL PL PT RU SV TR ZH ...
Страница 34: ...34 EN R6 R9 Quick installation guide R0 R4 R6 R9 R6 R9 EN DA DE ES FI FR IT NL PL PT RU SV TR ZH ...
Страница 42: ...42 EN Quick start up guide R0 R4 EN DA DE ES FI FR IT NL PL PT RU SV TR ZH ...
Страница 44: ...44 R6 R9 Quick installation guide R0 R3 R6 R9 EN DA DE ES FI FR IT NL PL PT RU SV TR ZH ...
Страница 47: ...47 DA DE ES FI FR IT NL PT RU SV TR CN R6 R9 Figures E 1 2 3 IP21 IP21 IP21 1 IP55 ...
Страница 48: ...48 DA DE ES FI FR IT NL PT RU SV TR CN 3AXD50000009286 Rev D ...