26 - AKD-6: Position Switch Actuator
Note: Later models of breakers (Q3 2015) are shipped with position switch bracket pre-
installed.
Position switch actuator bracket can be installed on AKR30H/50H versions of Emax 2 ACB for
AKD6 LVS. There are no additional parts to be instaled for AKR75/100 retrofill variants.
The steps of installation are as follows:
Retrofills use the legacy position switch already mounted in the cubicle. If a new position
switch has to be installed, refer to the legacy position switch installation manual.
1. Unpack the position switch bracket. Each bracket is provided with a pair of M6x16mm
Allen-type bolts and washers.
2. Place the bracket on the bottom right side of the AKD6 base. Two locating holes are
provided for mounting of the position switch bracket.
3. Fasten the two bolts to the locating holes after placing the washers to securely mount the
bracket.
4. The bracket is ready for use.
Figure 36
AKD-6 - Position Switch Actuator (Breaker Side) and Parts
Note
: Individual hardware for the position switch actuator cannot be ordered separately. The
item numbers given are for reference only. The assembly comes as a unit or a kit.
Level
Item or Part Number
Description
Quantity
1
10105289P1
Position Switch Brkt, AKD-6
1
1
10100950P4
Washer M6
2
1
10100380P1
Serrated Belleville Washer M6
2
1
10100545P1
Cap Head Screw M6x16
2
AKD-6 - AKR75/100
No Additional Parts Required
For Position Switch Actuator
©2022 Emax 2 Retrofill Circuit Breakers 800A-4000A 41
2TSA451014P0000 Rev-B
a
a
a
a