If you decide not to install the Retrofill breaker until a later time, then you can store it away
for installing it later.
1. Store the circuit breakers in a clean, dry location in an upright position.
2. Make sure that the breakers are properly supported to prevent bending of the studs or
damage to any of the breaker parts. Do not remove any protective grease until the
assemblies are ready to be installed. A covering of draft or other non-absorbent paper
prevents dust from settling on the breakers.
3. If breakers are not to be placed in service at once, remove them from their shipping
cartons and thoroughly inspect them for damage.
4. If everything is in satisfactory condition, replace the breakers in their shipping cartons
for storage. If it is necessary to store the equipment for any length of time, use the
following precautions to prevent corrosion or deterioration.
5. Store in a clean, dry, rodent-free location with moderate temperature and provide
protective coverings to prevent dirt, water, or other foreign substances from entering the
breaker.
6. If dampness or condensation is encountered in the storage location, heaters can be used
to prevent moisture damage.
7. After prolonged storage, Level 1 maintenance is needed under two years of storage. While
Level 2 maintenance is needed over two years of storage. Refer to circuit breaker manual
in maintenance L1-L2 descriptions.
Refer to Emax2 Installation, Operation and Maintenance Instructions – Publication
#1SDH001000R0002 pages 99
-
112
.
Notice
Store Circuit Breaker
PRODUCT DAMAGE
Do not store circuit breaker in corrosive
environments above LC1 (sea salt mist) and G1 as per
ANSI/ISA-S71.04-1985.
Ensure circuit breakers and cassettes are stored in a
clean, dry location, in their original packaging.
Failure to comply with these instructions may result
in product damage.
©2022 Emax 2 Retrofill Circuit Breakers 800A-4000A 19
2TSA451014P0000 Rev-B